• DOK-POWER*-KDV*2.3****-ANW1-EN-E1,44 • 06.97
Heat loss occurs when the KDV 2.3 is operated. This is caused by basic losses
during signal voltage generation, power losses and by energy transformation
in the bleeder.
The heatsink, which conducts this heat loss, is mounted to the back of the KDV
2.3. This means the KDV 2.3 is mounted with the heatsink sticking out of the
back of the control cabinet.
Note that the heatsink must maintain a safety clearance of 30 cm
from flammable materials or parts which could be affected by heat!
Heat loss
3. Guidelines for installation and electrical connections
The heat loss occurring within the control cabinet can be reduced to about
150 W with the above mounting mode. This means that more compact control
cabinets can be built. It also eliminates or minimizes the additional work due
to control cabinet air conditioning.
A bleeder cover SH-KD ist needed for the air duct and to cover the bleeder.
The heatsink blower can be ordered, with accessories, using order no. LE3-
... (LE3-220 with 220 V, LE3-115 with 115 V).
If several heatsinks are cooled in a common air duct with only one central
blower used, then make sure that there is sufficient air! Check air stream Q!
completely sealed housing or
cabinet
heatsink
Heat loss
air duct
external
internal
Kühlart
blower motor
air current
heatsink blower
KD...
P
Vint
P
Vext
Q = 32 l/s
P
max
= 50 Pa
V
air
= 3...4 m/s
Figure 3.14: A break down of the heat losses
Cooling with a heatsink
blower
Heat loss in the control
cabinet
Cooling with a central
blower