42 | Application Considerations SM Series Heat Pump
SM Series Heat Pump6 720 220 406 (2013/9) Subject to change without prior notice
open cooling tower may also be used. It is
imperative that all air be eliminated from the
closed loop side of the heat exchanger to insure
against fouling. In the heating mode, heat is
absorbed from the water loop. A boiler can be
utilized to maintain the loop at the desired
temperature.
Consult the specification sheets for piping sizes.
Do not overtighten the connections. Flexible hoses
should be used between the unit and the rigid
system to avoid possible vibration.
Ball valves should be installed in the supply and
return lines for unit isolation and unit water flow
balancing. Pressure/temperature ports are
recommended in both supply and return lines for
system flow balancing. Water flow can be
accurately set by measuring the water-to-
refrigerant heat exchangers water side pressure
drop. See specification sheets for water flow vs.
pressure drop information.
No unit should be connected to the supply or
return piping until the water system has been
completely cleaned and flushed to remove any dirt,
piping chips or other foreign material. Supply and
return hoses should be connected together during
this process to ensure the entire system is
properly flushed. After the cleaning and flushing
has taken place the unit may be connected to the
water loop and should have all valves wide open.
(Figure #104)
Figure # 104
[1] Line voltage disconnect (unit)
[2] Low voltage control connection
[3] P/T ports (optional)
[4] Hose kits (optional)
[5] Ball valves
[6] Supply and return line of central system
[7] Flex duct connection
[8] Hanging bracket assembly
[9] Threaded rod
[10] Hanging bracket assembly
Water piping exposed to extreme low
ambient temperatures is subject to
freezing.
Teflon tape sealer should be used when
connecting to the unit to insure against leaks
and possible heat exchanger fouling.
Diagram shows typical
installation and is for
illustration purposes only.
Ensure access to Heat
Pump is not restricted.