Configurability | 7SM Series Heat Pump
6 720 220 406 (2013/9)Revised 08-13
CONFIGURABILITY
HORIZONTAL CONFIGURABILITY
The Horizontal Configuration water source heat
pump is designed to have a field configurable
blower orientation: end blow (default) and straight
through. (Figure #4 and #5)
Figure # 4
Figure # 5
Required Tools
5/16" hex head driver
3/8" hex head driver
7/16" hex head driver
Flat screw driver
Phillips screw driver
1/4" hex head driver
Needle nose pliers
5/16”-1/4” ratchet wrench
Instructions - Left-Hand Unit (SM0**-
1HZ-*
L*-**)
1. Remove and retain end and side panels.(Figure
#6)
Figure # 6
2. Disconnect blower motor wiring and ground
wire fastened to blower housing.(Figure#7)
Figure # 7
Left-Hand and Right-hand Horizontal (HZ) units
have different Blower Configuration instructions.
---------------------------------------------------------------
Left- Hand unit instructions refer to Pg#7 and
Right-Hand unit instructions refer to Pg#10.
Internally mounted electric heat is only available
in End Blow configuration.
Blower configuration changes should be done
prior to unit being installed in the final location.
Discharge air configuration change is not
possible on Heat Pumps equipped with
Electric Heat Option.