Bosch D720W User Manual

Browse online or download User Manual for Numeric keypads Bosch D720W. D7412GV3 Control Panel - Bosch Security Systems

  • Download
  • Add to my manuals
  • Print
  • Page
    / 7
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Intrusion Alarm Systems | D7412GV3 Control Panel
D7412GV3 Control Panel
www.boschsecurity.com
u Fully integrated intrusion, fire, and access control
allows users to interface with one system instead of
three
u Conettix IP‑based communication options provide
high‑speed, secure alarm transport and control
through connection of up to two wired (DX4020)
and/or wireless (ITS‑DX4020‑G) network interfaces
u Eight programmable areas with perimeter and
interior partitioning
u 75 points with flexible configuration options to meet
multiple installation requirements
u Commercial Wireless allows up to 67 RF points
The D7412GV3 Control Panel delivers a powerful new
solution for intrusion, access control, and fire alarm
system applications. The control panel includes a
communicator that sends event reports to selected
public switched telephone network (PSTN), IP
network, or general packet radio service (GPRS)
destinations through four programmable route groups.
The control panel provides up to 75 individually
identified points. Each point:
Accommodates normally‑open (NO) and
normally‑closed (NC) devices with end‑of‑line (EOL)
resistor supervision
Is programmable for fire, fire supervisory, or intrusion
applications.
With the D7412GV3 you can:
Monitor alarm points for intruder or fire alarms while
operating user keypads and other outputs
Program all system functions locally or remotely
(attended or unattended) through Remote
Programming Software (RPS); pro-gram critical
parameters on site through a keypad.
Add up to two doors of access control using the
optional D9210BLC Access Control Interface Module.
Functions
Programmable Outputs
2 A alarm power at 12 VDC
1.4 A auxiliary power at 12 VDC
Four alarm‑output patterns
Automatic bell test
System Response
High performance micro‑controller provides
industry‑leading system response
31 custom point indexes, including fire supervisory
Selectable point response time
Cross point capability
Fire alarm verification
Fire inspector’s local test
Watch mode
Scheduled events (skeds) arm, disarm, bypass and
unbypass points, control relays, control authority
levels, and control door access
User Interface
Supervision of up to 16 keypads (up to 32
unsupervised keypads can be used)
Custom keypad text is fully programmable, including
remote programming
Page view 0
1 2 3 4 5 6 7

Summary of Contents

Page 1 - D7412GV3 Control Panel

Intrusion Alarm Systems | D7412GV3 Control PanelD7412GV3 Control Panel www.boschsecurity.com u Fully integrated intrusion, fire, and acce

Page 2

• Full function command menu including customfunctions• Authority by area and 16‑character name for eachuser• 14 custom authority levels control user’

Page 3

single frequency technology can only send informationon one narrow band channel. Any interference withinthe band can cause missed signals. With wirele

Page 4 - 4

ZX776Z PIR DetectorZX794Z Long Range PIR DetectorZX835 TriTech Microwave/PIR DetectorZX935Z PIR DetectorZX938Z PIR DetectorZX970 PIR/Microwave Detecto

Page 5

ISW‑EN1235SF Fixed‑location Transmitter (Double‑button)ISW‑EN1242 Smoke Detector‑TransmitterISW‑EN1247 Glassbreak Sensor‑TransmitterISW‑EN1249 Billtra

Page 6

Inovonics is a trademark of Inovonics Wireless Corporation.Ordering informationD7412GV3 Control PanelIncludes one printed circuit board (PCB) withmoun

Page 7 - D5500C-USB

D8109 Fire EnclosureRed steel enclosure measuring 40.6 cm x 40.6 cm x 8.9cm (16 in. x 16 in. x 3.5 in). UL Listed. Includes a lockand key set.Order nu

Comments to this Manuals