D9112 Installation and Troubleshooting Quick Reference
Page 3
Extra Points display default text:
If you incorrectly set the switches on a POPIT to a
point number that is not in your program for the panel, the default text for that point
number (
POINT ###
) displays when you fault the point. The
D9112 Program Record
Sheet
shows the default text for all points.
Faulting the point a second time produces the tone and displays thepoint text, but does
not reduce the
PTS TO TEST
count.
8. During the Service Walk Test you may want to see the points that remain untested. When
point text is displayed, press ESC. The display shows
## PTS TO TEST
. Press the ESC
key.
VIEW UNTESTED ?
is displayed. Press ENT.
## PTS UNTESTED
is displayed.
Press NEXT to see a list of the points that have not yet been tested. Move through this
list by pressing the NEXT key. To resume the Fire Test, press ESC.
## PTS UNTESTED
is displayed. Press ESC.
## PTS TO TEST
is displayed. Resume testing points. To end
the Service Walk Test, press ESC twice .
9. After testing the last point,
0 PTS TO TEST
displays. Press ESC. The display
momentarily shows
ALL PTS TESTED
before returning to idle text.
Automatic time-out returns the system to idle text:
If there is no point or command center
activity for 20 minutes, the walk test ends automatically. The command center returns to idle text.
(Text displays 60 seconds)
ENT
SERVICE WALK ?
IDLE TEXT
134 PTS TO TEST
Test a device
POINT TEXT
133 PTS TO TEST
Test a device
ESC
POINT TEXT
132 PTS TO TEST
Test a device
POINT TEXT
1 PTS TO TEST
Test a device
(Text displays 60 seconds)
0 PTS TO TEST
VIEW UNTESTED ?
ESC
ENT
# PTS UNTESTED
POINT TEXT
NEXT
ESC
ESC