17TSTBM3H2CPH6W-ATechnician Setup Menu
Tech Setup Step (Continued from the previous page)
LCD will show Adjustment Options
Factory
Default
Settings
Program
Options
You can congure this
thermostat to have a 7 day
program, a 5+1+1 program or
nonprogrammable.
Use the
or
+
keys to select 7d
for 7 day, 5d for 5+1+1, or 0d for
nonprogammable.
5d
Display Light
The display light can be
congured to come on when
any key is pressed or only
when the light key is pressed.
OFF congures display light to come
on only with the light key, which will
save battery power. ON congures the
display light to come on when any key
is pressed.
ON
Contractor
Call Number
Allows you to put your phone
number in the display. You
can choose ON or OFF
If selected ON, you will see the input
screen after pressing next step. Use
the
or
+
keys to select the desired
number and the FAN or SYSTEM
key to move from one character to
another. See note below on operation.
OFF
Beep
When any key is pressed an
audible beep will sound. You
can choose ON or OFF
If ON is selected the beep will sound.
If OFF is selected, there is no sound.
ON
Heat Pump
When turned on the
thermostat will operate a
heat pump.
1. EM.Heat will show as an
option in the system switch.
2. Y will be rst stage of
heat & cool, W/E will be
emergency heat relay & W2
will be auxiliary heat relay.
OFF congures the thermostat for non
heat pump systems.
ON congures the thermostat for heat
pump systems.
OFF
System
Switch
(only in HP
mode)
You can congure the system
switch for the particular
application:
Heat - Off - Cool,
Heat - Off,
Cool - Off,
Heat - Off - Cool-Auto
Note: EM. Heat will
show if in heat pump
mode.
Use the
or
+
keys until the desired
application is ashing.
Heat
- Off -
Cool
Fan
Operation
(not available
in HP mode)
Select GAS for systems that
control the fan during a call
for heat. Select ELEC to have
the thermostat control the
fan during a call for heat.
GAS or ELEC
If a system with electric heat is being
used, this setting MUST be set to
ELEC. When a call for heat is made,
the fan will not come on if set to GAS.
GAS