Tech Setup Step (Continued from the previous page)
LCD will show Adjustment Options
Factory
Default
Settings
Dehumidify
with AC
This feature forces the A/C to run
longer to remove humidity when
needed. The A/C will “over cool”
the room a few degrees until the
humidity reaches the desired
setpoint.
Use the
or
+
keys select YES or
NO.
If selected YES allows over
cooling to be used to control
humidity in Cool mode.
If NO is selected the system will
not use over cooling.
NO
Over Cool
Limit
°F, °C
The amount of over cooling
allowed when using A/C to
remove humidity. This screen is
only shown when ON is selected
in the “Dehumidify with AC” tech
setup step.
Use the
or
+
keys to select the
maximum number of degrees of
over cool.
Options are: 2, 3, 4, 5
3
HUM
Terminal
Options for how the Hum terminal
energizes.
Use the
or
+
key to select one
of the four options.
View the HUM Terminal chart
below for an explanation of these
options.
1
DHM
Terminal
Option for how DHM terminal
energizes.
Use the
or
+
keys to select one
of the four options.
View the DHM Terminal chart
below for an explanation of these
options.
1
Staging
Delay
This feature allows a delay to
occur when a second and third
stage is needed This allows the
previous stage extra time to
satisfy setpoint.
Use the
or
+
keys to select the
number of minutes to delay each
stage.
OFF 5, 10, 15, 30,45, 60,90 delay
minutes.
OFF
Satisfy
Setpoint
This feature allows the thermostat
to keep multiple stages of heat
or cool energized until setpoint is
satised
Use the
or
+
keys to select the
number of minutes to turn on or
off.
Technician Setup Menu