Quick Start Guide Subject to change without prior notice 8733914716 DDC (2014/02)
Quick Start Guide
GETTING STARTED
Perform a quick visual inspection to ensure the
controller has no external damage and all connectors
are intact. Ensure wiring is per desired application
(see sample FHP 560 wiring diagram on page 14).
Refer to I/O port conguration (page 13) for further
details on wiring inputs and outputs.
JUMPER SETTINGS
Verify that hardware conguration for jumpers
match corresponding Heat Pump system
application. If the controller is networked, ensure
communications jumper is set to EIA-485, unless
the network protocol is BACnet over ARC156.
Getting Started
Input Selection Jumpers for IN-1 & IN-2
(e.g. for a 0-5V CO2 Sensor
connected to IN-1, the jumper
should be set in bottom position)
IN-1 & IN-2 Jumper
Settings Label
Communications Selection Jumper
(i.e. jumper in bottom position for
BACnet over ARC156, or, jumper in top
position for EIA-485 using BACnet over
MS/TP, LON, Modbus, or N2 protocols)
Communications Selection label
In the above diagram, IN-1 and IN-2 are set to Thermistor/Dry
Contact, and Communications is set to BACnet over ARC156.