Horizontal and vertical flue
terminal positioning
Flue terminal positions
for water heaters in accordance
with AS/NZS5601.
3 The water heater must be installed so that the terminal
is exposed to the external air
3 It is important that the position of the terminal allows
the free passage of air at all times
3 Minimum acceptable spacing from the openings are
specified above, for domestic situations in accordance
with AS/NZS5601
Key to illustration
Balanced flue terminal position
Terminal Position
Minimum
Spacing
A
Directly below, above or alongside an opening
window, air vent or other ventilation opening
1,500mm
B Below guttering, drain pipes or soil pipes 75mm
C Below eaves 300mm
D Below balconies or a car port roof* 300mm
E From vertical drain pipes or soil pipes 75mm
F From internal or external corners 300mm
G Above adjacent ground, roof or balcony level 300mm
H From a surface facing the terminal 1,500mm
I From a terminal facing the terminal 1,200mm
K Vertically from a terminal on the same wall 1,500mm
L Horizontally from a terminal on the wall 300mm
M Adjacent to opening 1,500mm
N Above intersection with roof 500mm
O For a vertical structure on the roof 500mm
A
F
M
G
M
B,C
F
B,C
K
G
C
L
A
N
N
O
E
J
K
D
F
K
G
G
G
H, I
K
L
Technical & Specification Information – Bosch 32 Series Water Heaters
|
27