Bosch DANESMOOR UTILITY 32-50 Instruction Manual Page 35

  • Download
  • Add to my manuals
  • Print
  • Page
    / 52
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 34
%CO
2
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
USING 28sec KEROSENE:
NOZZLE
OIL
PUMP
PRESSURE
(p.s.i.)
FUEL
FLOW RATE
Kg/h l/h
COMBUSTION
HEAD
SETTING
APPROX.
AIR
SETTING
APPLIANCE
INPUT OUTPUT
kW Btu/hr kW Btu/hr
Bentone Sterling 146 Burner (50/70kW):
1.25 45° S
1.50 45° S
2.00 45° S
145/150
145/150
110/135
4.33
5.2
6.05
5.48
6.58
7.66
80
85
90
12.0
12.0
12.0
6.0
9.0
13.0
50
60
70
52.1
62.5
72.9
Bentone Sterling 133 Burner (32/50kW):
0.85 60°ES
1 .10 45 ° S
1.35 45° S
150/-
120/-
155/-
2.78
3.55
4.33
3.52
4.49
5.48
75
85
95
11.5
12 . 0
12 . 5
2.0
4.0
8.0
114000
146000
178000
178000
213000
249000
32
41
50
110000
140000
170000
33.4
42.7
52.1
N/A
N/A
N/A
APPROX
FLUE
GAS
TEMP.
( °C )
N/A
N/A
N/A
170000
205000
240000
STARTING THE APPLIANCE
BENTONE STIRLING BURNERS
2 Fit a suitable pressure gauge to port (A) on
the oil pump.
Adjust the air shutter (F) and pump pressure
(B) as shown in the table below. The
burner should ignite following a pre-ignition
period of approx. 15 seconds.
Boiler lockout indicator on:
If the burner fails to establish a normal firing
pattern or flame failure occurs the flame
monitoring photocell mounted in the burner
body will alert the burner control box to shut
the burner down and provide a safe lockout
state indicated by the illumination of the lock-
out indicator/reset button (E).
Wait 2 minutes then press the lockout
indicator reset button (E) to initiate another
start sequence.
Repeat procedure until a flame is established.
3Start and run for 3 minutes then switch off.
Check for after-spurting from the nozzle,
indicated by oil saturation on the combustion
head (G).
If after-spurting occurs:
Release the burner retainers (H).
Remove the burner, combustion head (G).
and electrodes, hold the burner vertical
to unscrew the nozzle (K) and fill the nozzle
holder ( J ) with kerosene.
Refit nozzle (K), electrodes, combustion
head (G) and the burner.
Restart and run for 3 minute intervals until
after-spurting stops.
4Start and run for 20 minutes.
Remove sampling point plug ( L ) to check
the smoke reading is between 0-1. If the
smoke level is above 1, check the combustion
settings are correct and the oil nozzle is in
good condition.
NOTE: smoke readings may be inaccurate
until the smoke from burning organic binder in
the access door insulation has ceased.
Check the CO
2
levels and adjust the air
shutter (F) setting according to the table
opposite.
Check the flue gas temperature is close to
the values shown in the table.
If the flue gas temperature is too high and the
baffles are correctly fitted, then reduce the oil
pump pressure (B) 5-10p.s.i. to compensate
for nozzle variations.
Turn off the electrical supply.
Isolate the oil supply to the burner.
Remove the oil pressure gauge.
Refit the blanking plug (A).
Check and rectify any oil leaks.
5Switch on the oil supply.
Switch on the electrical supply.
Restart the boiler and run for 5 minutes.
Recheck the CO
2
levels and if required,
adjust the air shutter setting (F) to obtain
the correct CO
2
level.
Repeat the fine tuning procedure (5) if required.
Refit the sample point cap (L)(hand tighten
only, do not over tighten).
STARTING THE APPLIANCE
BENTONE STERLING BURNERS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR UTILITY 32/50 & 50/708 716
109 711B 07.2010
35
COMMISSIONING
8 716 109 711 b 07.10 14/7/10 09:59 Page 35