FAULT FINDING
PROBLEM CAUSE REMEDY
FAULTY BOILER
OPERATION:
Noisy operation Pump noise from air in pump or
worn pump
Bleed air from pump or replace pump
Worn motor bearings Replace motor
Fan out of balance Replace fan
Boiling Faulty boiler thermostat Replace if necessary
Short circuit boiler thermostat Temporarily take out of circuit to check
Thermostat bulb not fully home in
pocket
Ensure bulb is pushed fully home
No primary water circulation Check system / circulating pump
Short Cycling Burner rating incorrect Correct burner rating
Boiler thermostat differential
incorrect
Replace boiler thermostat
External controls not operating
correctly
Check and correct external controls
OIL SMELLS: Blocked flue, fumes on startup CF - Check flue with gauge and check
seals/gaskets
RS - Check seals/gaskets
Oil soaked boiler, faulty burner
operation, numerous lockouts
Rectify burner operation and lockouts
Odour in boiler room, oil leaks
from pipework, flexible hoses
connections
Rectify oil leaks, replace components i
f
necessary
FAULT FINDING
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR UTILITY 32/50 & 50/708 716
109 711B 07.2010
47
FAULT FINDING
& DIAGRAMS
8 716 109 711 b 07.10 14/7/10 09:59 Page 47