System pressure
Greenstar Ri Compact
ErP
- 6 720 813 339 (2014/09)
4.3 External filling loop
Once the external filling loop has been located, follow the instructions for re-pressurising the system.
1. Unscrew blanking cap.
2. Attach the hose to the valves, screw on hand-tight.
3. Turn the handle/screwdriver slot through 90° to open the valves.
4. The handle/screwdriver slot will be in-line with the valves
Fig. 4 External filling loop
5. When the pressure reaches between the 1 and 1.5 bar marks (zone A), turn the handle/screwdriver slot back, through 90°, to
close the valve.
6. The handle/screwdriver slot will be at 90° to the valves
7. Remove the hose and replace the blanking caps.
NOTICE: External filling loops
If the filling loop does not look like the one shown in the figure below or you cannot find your filling loop, contact
your installer.
To comply with Water Authority regulations you must disconnect the external filling loop after re-
pressurisation.
If the pressure gauge reads more than 1.5 bar as a result of over filling, bleed one radiator until the pressure gauge
returns to between 1 and 1.5 bar.