LBB 1938/20 Plena Power
Amplifier
Features
480 W power amplifier in a 3U high 19”housing
70 V / 100 V and 8 ohm outputs
Dual inputs with priority switching
100 V input for slave operation on 100 V speaker line
Temperature controlled forced front to back
ventilation, directly stackable
Mains, battery back-up, and pilot tone supervision
EN 54‑16 and EN 60849 compliant
The LBB 1938/20 is a powerful 480 W power amplifier in a
3U high 19”case for rack mounting or tabletop use. LEDs
on the front panel show the status of the amplifier:
power, audio output level, and supervised functions. This
high-performance unit fulfills a wide range of public
address requirements at a surprisingly low cost.
Functions
Dependability
The amplifier is protected against overload and short
circuits. A temperature-controlled fan ensures high
reliability at high output levels and low acoustic noise at
lower output levels. An overheat protection circuit
switches off the power stage and activates an LED on the
front panel, if the internal temperature reaches a critical
limit due to poor ventilation or overload.
The unit operates both on mains power and on a 24 V
battery power supply for emergency back up, with
automatic switchover.
For emergency and evacuation use, the following
functions are monitored: mains presence, battery present,
pilot tone presence, amplifier operation. Front panel LEDs
indicate the status of supervised functions. The LEDs of
pilot tone supervision and battery status can be switched
off for general public address use. Failsafe (normally
energized) relays are provided for each supervised
function. These relays are always active regardless of the
switches on the rear panel.
Input
The system has two balanced inputs with priority control,
each with a loop-through facility. This makes it easy to
connect remote systems that require priority control. An
additional 100 V line input is provided to connect the
amplifier to a 100 V loudspeaker line, to provide more
power to remote locations.
Gain or level control is located on the rear of the unit to
avoid accidental setting change. A meter with LED-bar
shows the output level.
Output
The amplifier has 70 V and 100 V outputs for constant
voltage loudspeaker systems and a low impedance output
for 8 ohm loudspeaker loads.
The LBB 1938/20 has two separate priority controlled 100
V outputs for zones that only need announcements made
via the priority input, and for zones that will not get any
announcements made via the priority input.
Controls and indicators
Front
Meter (LED's for -20, -6, 0 dB and Power ON)
Battery operation indicator
Overheat indicator
Air inlet for forced air cooling
Back
Level control input 1
Level control input 2
Power button
Mains switch
Interconnections
Back
Priority line input 1 (XLR/balanced)
Line loop-through 1 (XLR/balanced)
Program line input 2 (XLR/balanced)
Line loop-through 2 (XLR/balanced)
Priority controlled loudspeaker output terminals
24 VDC power supply terminal
Three loudspeaker direct output terminals
Two 100 V slave input terminals
Input 2 enable control terminal
Input 1 priority control terminal
Earth connection screw
Mains socket
Certifications and Approvals
Region Certification
Europe CE
Poland CNBOP