Server/Client Operation (Continued)
TCP/IP Networks. The minimum recommended
connection speed for TrueSite Workstation Server or
Remote Client to a TCP/IP local area network is 3 Mbps.
Anti-Virus Software. When either the TrueSite
Workstation Server or Remote Client computer is
connected to a TCP/IP network other than a dedicated
Fire Alarm network, it is highly recommended that
regularly updated anti-virus software protection be
installed on each connected computer. The TrueSite
Workstation has been verified as compatible with
Symantec EndPoint Protection 12.1 and McAfee
Enterprise 8.8.
Additional Reference
Description Document
Installation and Checkout Instructions 579-834
Operation and Application instructions 579-835
Software Upgrade Instructions 579-838
TrueSite Workstation Configurator Reference
Manual
579-844
Quick Reference Operator Instructions 579-878
TrueSite Workstation Parts List 579-888
TrueSite Workstation 3rd Party Interface
Software Customer Information Form
579-1155
Localization Procedure 579-946
Release Notes 579-1018
TSW Mobile Client User Guide 579-1154
General System Listings Reference
The following functions are agency listed with the
computers and monitors identified under Product
Selection on page 7:
TrueSite workstation PCs, whether stand-alone or
functioning as a server to remote clients
Supervised Remote Clients with protected features
that are connected to the server using a dedicated Fire
Alarm Network as described on page 10
Refer to data sheet S4190-0018 for details about Fire
Alarm Network Ethernet Switches
Additional agency listings reference:
Restricted feature Remote Clients software on
compatible computers (listed for standard office use)
provide annunciation features only and can be
connected using a facility LAN without system listing
impact
Mass Notification Systems Reference
The TrueSite Workstation operates as a UL 2572 listed
Central Command Station (CCS) when configured per the
following:
1. Select model 4190-8401 (Note: Cannot be used for
Supervising Station or Security Monitor applications)
2. Provide an audio system microphone mounted
adjacent to the TrueSite Workstation, either
located within a 4100ES (or 4100U) Fire Alarm
Control Panel or Remote Annunciator Panel, or use a
Remote Microphone Assembly.
3. The 4100ES/4100U microphone options are Model
4100-1243 for Fire Alarm Control Panels and Model
4100-1244 for Remote Annunciator Panels (refer to
data sheet S4100-0034 for details).
4. Remote Microphone Assembly Model 4003-9803
mounts separate from the control panel (refer to data
sheet S4100-0053 for details).
5. Note: At least two monitors must be connected to
provide the necessary display information (see
exception below). One monitor is required to display
the speaker zone status and the other monitor is
required to display the event screen.
6. Exception: If a 4100ES/4100U Network Display
Unit (NDU) is mounted adjacent to the TrueSite
Workstation for network audio control with
microphone access, a second monitor may not be
necessary if the audio control status is viewable.
Review the application with the local authority
having jurisdiction (AHJ).
11 S4190-0016-30 3/2015