Heat transfer fl uid out max T8 (GT8)
Sensor T8 (GT8) in the heat pump stops the compressor if the temperature
of the water going out to the heating system becomes too high.
Possible cause 1: Insuffi cient fl ow over the heat pump.
Action: 1. Check that the heating system pump has not
jammed.
2. Check that all the valves are open. Radiator ther-
mostat valves should be fully open and underfl oor
heating systems should have at least half of the
coils fully open.
Possible cause 2: The fi lter on the primary circuit is blocked.
Action: 1. Clean the fi lter.
The heat pump starts automatically
when the alarm is reset and the water
temperature has dropped to its normal
value.
Note
What to do if a fault occurs
ALARM (GT8)
Heat tran uid out
060822 16:08:15
Info Ackn.
HTF in under limit T10 (GT10) and HTF out under
limit T11 (GT11)
Possible cause 1: Temporary low heat transfer fl uid temperature.
Action: 1. Monitor performance of the heat pump.
2. If the alarm returns, contact the Technical Support
Department.
Possible cause 2: Too low fl ow on the collector circuit.
Action: 1. Check the fi lter.
2. Clean the fi lter if it is blocked.
Possible cause 3: The minimum heat transfer fl uid temperature has
been set too low.
Action: 1. Monitor performance of the heat pump.
2. If the alarm returns, contact the Technical Support
Department.
Sensor fault
All sensors connected to the heat pump can give an alarm when defective. In the
example to the right it is sensor T1 (GT1), Return radiator, which has given an
alarm. All sensors give alarms in the same way. Read more about the sensors
under heading Read the temperatures on the heat pump.
Possible cause 1: Temporary error.
Action: 1. Monitor performance of the heat pump.
Possible cause 2: Short circuit or broken sensor cable.
Action: 1. If you have a multimeter you can disconnect the sensor
and check the cable’s resistance. Compare with the
sensor table in the section Technical information.
Possible cause 3: Defective sensor or incorrect connection.
Action: 1. Replace sensor/check connection.
Switch off the power before checking
the resistance of the cable.
Note
ALARM (GT1)
Sensor return rad.
060822 16:08:15
Info Ackn.
ALARM (GT10)
HTF (coll) in
060822 16:08:15
Info Ackn.
ALARM (GT11)
HTF (coll) out
060822 16:08:15
Info Ackn.