Detection Systems, Inc. Copyright © 2001 Detection Systems, Inc.
130 Perinton Parkway, Fairport, New York, USA 14450-9199 DS9370 Installation Instructions
(585) 223-4060 • (888) 289-0096 • Fax: (585) 223-9180 P/N: 48781C 2/02
11.0 Optical Module Adjustment
The PIR zones of the DS9370 are divided into three groups. Each of these 3 groups can be independently adjusted vertically to
provide the best coverage within a room.
Only two coverage patterns are shown for clarity. PIR vertical adjustment knobs
Use the following chart to adjust the optical modules based on the mounting height of the detector. The range shown is the distance
from the detector to the outside edge of the coverage pattern.
Mounting Height
Feet (Meters)
Maximum
Range
Feet (Meters)
8 (2.4) 10 (3) 12 (3.7) 14 (4.3) 15 (4.6) 16 (4.9) 18 (5.5) 20 (6.1) 22 (6.7) 24 (7.3) 25 (7.6)
10 (3) C A
15 (4.6) G D A A
20 (6.1) I G D B A A
25 (7.6) I F E D C A A
30 (9.1) H F E E C B A
35 (10.7) I G G F E C B A A
In installations where a targeted coverage is required for part of the area, the optical modules must be adjusted for the correct
coverage. In the example below, the detector is mounted 12 ft. (3.7 m) above the floor. The distance to one wall is 20 ft. (6.1 m) and 35
ft. (10.7 m) to the opposite wall. Using the chart above, the optical module for the 20 ft. (6.1 m) range was set to "D" and the optical
module for the 35 ft. (10.7 m) was set to "I".
Only two coverage patterns are shown for clarity.
-
+
NO C
NC T T M
MAX PIR Signal
Gain
12 ft.
(3.7 m)
20 ft.
(6.1 m)
35 ft.
(10.7 m)