Bosch Plena Voice Alarm System User Manual Page 7

  • Download
  • Add to my manuals
  • Print
  • Page
    / 11
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 6
Plena Range | 61
www.boschsecurity.com
Communication
Technical Specifications
Electrical
Mains Voltage 230 VAC / 115 VAC,
±15%, 50 / 60 Hz
Max Mains Power
Consumption
50 VA
Battery Voltage 20 – 26.5 V
Max Battery Current 1.8 A
Max Mains Inrush Current 1.5 A @ 230 VAC / 3A @ 115 VAC
Power Consumption
Mains Current
System Idle 0.2 A
Maximum Load 0.3 A
24 V Current
System Idle 0.51 A
Maximum Load 24 V Output 1.5 A
Trigger Inputs 6 EMG, 6 business
Type MC1, 5/12-ST-3, 5
Activation Programmable
Supervision On EMG inputs, programmable
Supervision Method Series / parallel resistor
100 V Inpu ts MSTB 2,5 /16-ST
Booster 1 100 V / 70 V / 0 V
Booster 2 100 V / 0 V
Power Handling Capacity 1000 Watts
Outputs
100 V / 70 V Outputs MSTB 2,5 /16-ST, floating
100 V Outputs 1000 W rated per zone
Volume Override Type 3 wire, 4 wire (24 V),
4 wire failsafe
Output Contacts
All Contacts
Connector Type MC1,5/12-ST-3,5
Rating 250 V 7A voltage free
General Purpose Relays (2x) NO / COM
Environmental
Operating Temperature +5°C to +55°C
Storage Temperature -25°C to +55°C
Relative Humidity <95%
Dimensions 88 x 430 x 260 mm
(19" wide, 2U high)
Weight approx. 3 kg
Rack Building Rack mounting kit included
Ordering Information
Model & Description
LBB 1992/00 Plena Voice Alarm Router
Page view 6
1 2 3 4 5 6 7 8 9 10 11

Comments to this Manuals

No comments