Bosch D1255RB User Manual Page 17

  • Download
  • Add to my manuals
  • Print
  • Page
    / 30
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 16
GV4 Series | Approved Applications Compliance Guide | 6.0 System Wiring Diagrams
Bosch Security Systems, Inc. | 3/12 | F01U266055-01 17
6.0 System Wiring Diagrams
The System Wiring Diagrams, (refer to Figure 4: GV4 Series Power Supply Side System Wiring (Power
and Phone) on page 17 to show the relationship between the control panel and the accessory
components referred to in Table 3 on page 16).
6.1 Power Supply Side System Wiring Diagrams
All external connections except Terminal 5 (battery positive) are power limited.
Figure 4: GV4 Series Power Supply Side System Wiring (Power and Phone)
1 - If required by local AHJ, connect D113 Battery Lead
Supervision Module.
2 - Batteries
3 - D122/D122L Dual Battery Harness, as required
4 - D1640 Transformer and D8004 Transformer
Enclosure required for NFPA Applications
5 - D8132 Dual Battery Charger with two batteries
(Batteries are not supervised.)
6 - D192G Bell Supervision Module
7 - To Relay A or Relay B
8 - Listed Audible Signaling Devices rated at
12.0 VDC nominal (do not use vibrating
type horns)
9 - C900V2(optional)
10 - RJ31X, secondary phone line (not available on
the D7212GV4)
11 - 560 Ω, 2 W EOL Resistor
(P/N: 15-03130-005)
12 - RJ31X, primary phone line
13 - D928 (not available on the D7212GV4)
14 - To earth ground
Terminals 1, 2, and 11, and the Accessory Connector are power limited, supervised.
All external connections except Terminal 5 (battery positive) are power limited.
Page view 16