Bosch WLSD3000 Service Manual

Browse online or download Service Manual for Smoke detectors Bosch WLSD3000. Bosch WLSD3000 User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 2
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Installing and Operating Instruction Model S Smoke Detector
Manual-RWMS-E-1001629, Edition 10012011 side 1
Functional Characteristics
Battery run smoke detector operating according
to the Tyndall effect
Suitable for installation in mobile recreation
vehicles (subject to extended testing according to
DIN EN 14604 for a high resistance to changing
temperatures)
Elevated range of temperature from -10
o
C … up
to 60
o
C
Smoke intrusion conduct exactly specified
Secured against false alarm by powerful
measuring chamber Instant and fail-safe fire
detection due to exact alignment of the triggering
parameters
Enhanced operating security due to intelligent
signal analysis of the measuring chamber
Elaborated automatically generated self control of
the electric system
Interface for optional upgrade with a radio- or a
relay-module
Environmental friendly operation due to
replaceable batteries
Interface to Radio-Controlled Fire Alarm
System
The smoke alarm detector comes with an interface
enabling an optional upgrade to various SeCa radio-
controlled fire-alarm systems (e.g. SeCa Power Line, SeCa
CC100PREMIUM…)
Relay Module
Interface for a relay module to connect to an external
sensor or coupling to an EIB etc.
For detailed information please consult the corresponding
manual.
Function Principle
The smoke alarm detector will identify a fire early,
detecting its smoke emission. It works according to the
scattered light principle (Tyndall-effect): the arrangement
of light emitters and receivers inside the measuring
chamber keep emitted light signals from hitting straight
into the receiver (optical cell). Should smoke enter inside
the box through the smoke inlet apertures the floating
smoke particles will scatter the light signal. Those
scattered light rays will hit the optical cell and be
transformed into an electric signal. The fire alarm will be
triggered. Functioning of smoke evaluation is constantly
checked. Potential nonconformities will be notified by
malfunction signals (acoustic signal or LED).
.
Operating and Alerting Signals
Signal
meaning
Acoustic
signal
LED
--
flash every
40s
automatic self-testing,
normal operating mode
sonorous
interval
tone
flashes twice
local smoke alarm or
functional test
sonorous
interval
tone
-
smoke alarm at a
networked smoke
detector
Short signal
tone every
40s
flash,
alternating
with acoustic
signal
malfunction / pollution
Short signal
tone every
40s
flash
according to
acoustic
signal
indicates battery
replacement
Serial Number and Type Label
Maintenance and Support
Installation and maintenance of the devices have to
comply with DIN 14676 including a leastwise annual
maintenance, a visual inspection, a functional test as well
as a replacement, if indicated, of the battery. Please refer
also to description page 2.
Please Note
1. Do not use rechargeable batteries or power
supply units.
2. The smoke alarm detector generates a sharp,
piercing tone that might damage your sense of
hearing. Please keep a minimum distance of
50cm between smoke alarm detector and your
ear whilst testing the unit.
3. Do not paint the unit.
4. The smoke alarm detector is not to fit in rooms
below a temperature of -10
o
C or superior to
60
o
C.
5. The smoke alarm detector should not be
mounted onto environments like:
5.1. spaces that generate strong emissions
of steam (e.g. kitchens, bathrooms,
lavatories)
5.2. spaces near fireplaces and firesides
5.3. vicinity of flues (e.g. near air condition
or circulated air systems)
5.4. gables (e.g. pediments)
6. Please keep an installation distance of 50cm
minimum to light bulbs.
7. The smoke alarm detector is admitted for indoor
use only.
Page view 0
1 2

Summary of Contents

Page 1

Installing and Operating Instruction Model S Smoke Detector Manual-RWMS-E-1001629, Edition 10012011 side 1 Functional Characteristics  Battery ru

Page 2

Installing and Operating Instruction Model S Smoke Detector Manual-RWMS-E-1001629, Edition 10012011 side 2 Installation and Commissioning 1. Ass

Comments to this Manuals

No comments