DX4010i | Installation Instructions | 6.0 Remote Programming Direct Connection
Bosch Security Systems, Inc. | 1/05 | 4998141106C 7
5.3 Address DIP Switches
The address DIP switches are used to assign an address
to the DX4010i.
Refer to Table 3 for DIP switch option bus address
settings.
Refer to Table 4 for DIP switch SDI bus address
settings.
Refer to Figure 7 for proper DIP switch orientation.
Figure 7: DIP Switch Location and Orientation
ON
123 456
12481632
78
64 128
4
3
2
SER
RxTx
BUS
RxTx
LED
ENAB LE
DB9 G ND
ENABLE
P1
P6
P2
P3
1
1- Address DIP switches
2- ON position
3- OFF position
4- Address example (option bus Address 0)
6.0 Remote Programming
Direct Connection
The DX4010i can be used to create a local direct
connection for remote programming of a compatible
control panel.
Option Bus: Set the address DIP switches to
Address 0. Refer to Table 3 on page 8.
SDI Bus: Set the address DIP switches to Address 88.
Refer to Table 4 on page 9.
Consult your control panel’s installation guide for
specific wiring connections.
A DB9 to DB9 null-modem cable is
required when using the direct connection
method.