6 720 644 951 (2014/11) 330 PN
18 | Installation instructions
* EHD = Equivalent Hydraulic Diameter. The greater the value
EHD, the greater the gas capacity of the tubing.
Maximum Capacity of Semi-Rigid copper Tubing in Thousands
of BTU per Hour of Undiluted Liquefied Petroleum Gases (at 11
inches Water Column Inlet Pressure).
(Based on a Pressure Drop of 0,5 inch Water Colunm).
* Source National Fuel Gas Code NFPA 54, ANSI Z223.1
- No Additional Allowance is necessary for an ordinary number
of fittings.
Tube size
inches
EHD*
Lenght of Flexible Corrugated Stainless Steel Tubing (CSST), Feet
10 20 30 40 50 60
1/2 18 129 91 74 64 58 53
3/4 23 254 183 151 131 118 107
1 30 521 365 297 256 227 207
1 - 1/4 37 971 661 528 449 397 359
Table 9
Nominal
Iron Pipe
Size
inches
Black Iron Pipe
Lenght of pipe, Feet
10 20 30 40 50 60 80 100 125 150 200
1/2 291 200 160 137 122 110 94 84 74 67 58
3/4 608 418 336 287 255 231 197 175 155 140 120
1 1145 787 632 541 480 434 372 330 292 265 227
Table 10
Outside
diameter
Inch
Cooper (LP gas only)
Lenght of Tubing, feet
10 20 30 40 50 60 70 80 90 100
3/8 39 26 21 19 - - ----
1/2 92 62 50 41 37 35 31 29 27 26
5/8 199 131 107 90 79 72 67 62 59 55
3/4 329 216 181 145 131 121 112 104 95 90
Table 11