24 en | Connection Battery Charger
180110011Aa | V1.1 | 2011.05 Installation and Operation manual Bosch Security Systems B.V.
6.6 Connect the temperature sensor
The battery charger has one socket to connect the temperature sensor (which is packed with
the system).
1. Plug the temperature sensor into the temperature sensor socket.
2. Attach the sensor body close to the battery, with good thermal coupling in order to get
the correct temperature information. E.g. connect the sensor to the battery tray, or place
it between the batteries. See Figure 6.6.
Figure 6.6 Connect the temperature sensor
6.7 Connect the mains
The battery charger is able to connect to 230 Vac +/- 15%.
6.7.1 Mains power cable
1. Use the supplied lockable mains connector to assemble a locally approved mains cable.
2. Connect the mains cable to the battery charger.
6.7.2 Ground connection
1
7
89
23
4
56
6
CAUTION!
Applied charging voltages and current are temperature dependant. Therefore always use the
temperature sensor. If the temperature sensor is not used (or not used correctly), this can
damage the battery, or reduce the lifetime of the battery. Refer to section 8.1.4 .
NOTICE!
If the temperature sensor is not connected, broken or has a short circuit, the voltage is
compensated for 25°C. Refer to section 8.1.4 .
NOTICE!
Use a mains circuit breaker to connect or disconnect the battery charger from the mains.
CAUTION!
Make sure that the safety ground is connected to the battery charger via the mains power
cable.
CAUTION!
Do not make a separate ground connection to the battery.