Control PanelD9412GV4/D7412GV4 v2.03 en UL Installation Instructions
Figure 2.3: Reset PinCallout - Description1 - Reset pin locked (closed)2 - Reset pin normal (open)10 en | Installation Control Panel2014.04 | 03 | F.0
DiagramsFaceplatesFigure 3.1: FaceplatesCallout - DescriptionCallout - Description1 - Charging status LED (yellow) 8 - Ring2 - Low battery LED (red) 9
Power Supply Side Wiring DiagramsD9412GV4/D7412GV4 v2.00 (and higher) Power Supply Side System(D113, D122/D122L, D192G, D928, D1640, D8132) Wiring Dia
Notice!For UL Certified accounts, additional power can be obtained using only a UL Listed auxiliary12.0 VDC regulated, power-limited power supply.Noti
D9412GV4/D7412GV4 v2.00 (and higher) Input Points andPeripheral Devices (D125B, D129, D130) System WiringDiagramSw. Aux PwrZone BZone APnl CommonPnl C
SDI and Zonex Devices Wiring Diagrams D9412GV4 SDI and Zonex Devices (B420/B426, B450, D1255/D1255RB,D1256RB, D1257RB, D1265, D8125, D8128D, D8129, D
Callout ᅳ Description Callout ᅳ Description5 ᅳ Up to 119 D9127U/T POPITs 1The number of D8129 OctoRelays that can be connected to each Zonex terminal
6 - Zonex 1: Up to 9 D8128Ds maximum7 - Zonex 1: Up to 8 D8129s maximum11The number of D8129 OctoRelays that can be connected to each Zonex terminal o
D9412GV4/D7412GV4 CapacitiesModule D9412GV4 D7412GV4B208 Octo-input Modules 24 71B308 Octo-output Modules 12 62B420/B426 Conettix EthernetCommunicatio
SDI2 Bus Wiring RecommendationsUse the following SDI2 bus wiring recommendations for SDI2 installation. The SDI2 bus isused by the GV4 Control Panel
CablecapacitanceOverallcablelength CablecapacitanceOverallcablelength CablecapacitanceOverallcablelength CablecapacitanceOverallcablelengthpF/ft ft
Keyswitch WiringFigure 3.9: Keyswitch WiringCallout - Description1 - Maintained keyswitch2 - Momentary keyswitch3 - Common4 - Point Input5 – End of Li
Power Supply and Power OutputsPower Supply - PrimaryPrimary (AC) Power CircuitThe primary source is a 16.5 VAC, 40 VA, internally-fused transformer (B
D8004 Transformer Enclosure Required for Fire SystemsUse the D8004 Transformer Enclosure for the D1640 Transformer in fire and combined fireand burgla
!Warning!High current arcs are possible. The positive (red) battery lead and Terminal 5 can create highcurrent arcs if shorted to other terminals or t
Figure 4.2: Non-PowerLimited WiringCallout ᅳ Description1 ᅳ Conduit required for use with external batteries.2 ᅳ Battery wires3 ᅳ 0.25 in (6.4 mm) min
– Terminal 8: Output C (Switched Auxiliary Power)PTC CB5 protects Terminal 24: Zonex Power.PTC CB1 protects Terminal 32: SDI Power +.PTC CB3 protects
F01U265459) contains complete instructions for programming outputs. Refer to Terminals 6and 7, page 27, Fire System Power Formula, page 27, and Termin
Terminal 8Terminal 8 provides continuous positive (+) 12.0 VDC Nominal power. Output C interrupts thepower at Terminal 8 when activated. Use Terminal
SpecificationsVoltage Input(Power Supply)1Primary: Terminals 1 and 2 16.5 VAC 40 VA class 2 plug-intransformer (D1640)Secondary: Terminals 4 and 5 Sea
Table of contents1Introduction 51.1 About documentation 51.2 Bosch Security Systems, Inc. product manufacturing dates 52Installation 62.1 Installation
SDI Bus B-: 9 VDC 15000 ft (4572 m) maximumSDI2 Bus SDI2 Bus A+; 12 VDC nominal 7500 ft (2286 m) maximum3SDI2 Bus B-: 12 VDC nominal 7500 ft (2286 m)
B520 SpecificationsVoltage Input (PowerSupply)Primary: 18 VAC terminal 18.0 VAC, 50 VA class 2 plug-intransformer -TR1850(18.0 VAC, 50 VA class 2 plug
Recharge Cycle AC ON – Load shed relay resets, battery chargingbegins, Battery Trouble and AC Restoral Reportssent.12.6 VDC – Battery Restoral Report
TerminalNoTerminalDescriptionRequirements16 POINT 4 Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loopresistance less than 10
TerminalNoTerminalDescriptionRequirements36 SDI2 POWER Terminal accommodates 14 to 22 AWG, use appropriate wire size based on peripheraldevice current
Compatible Accessories1Model Title UL 864 UL985Intrusion cULIntrusionD162 Phone cord D185 Reverse Polarity Module X X X D192G Bell Circuit Sup
Compatible Accessories1Model Title UL 864 UL985Intrusion cULIntrusionZX970 PIR/Microwave Motion Sensor with POPIT X RFBT-A3RADION speciality
Circuit ClassesOnboard PointsOnboard points, points 1 to 8, are Class B, Style B Initiating-Device Circuits.Zonex Bus or BusesZonex buses are Class B,
4.6.4 Terminal 8 285Specifications 295.1 B520 Specifications 315.2 Terminal Wiring Requirements 325.3 Compatibilities 345.4 Circuit Classes 374 en | T
Bosch Security Systems, Inc.130 Perinton ParkwayFairport, NY 14450USAwww.boschsecurity.com© Bosch Security Systems, Inc., 2014
IntroductionAbout documentationCopyrightThis document is the intellectual property of Bosch Security Systems, Inc. and is protected bycopyright. All r
InstallationInstallation PreparationThis section contains a general installation procedure and refers to other sections of thedocument for detailed in
Notice!Electromagnetic interference (EMI) can cause problems on long wire runs.Figure 2.1: Enclosure MountingCallout - Description1 - Point chart labe
Connecting Earth GroundTerminal 10To help prevent damage from electrostatic charges or other transient electrical surges,connect the system to earth g
Figure 2.2: Ground Fault Detect (S4)Callout - Description1 - S4 Locked (Closed). Control panels detects ground faults.2 - S4 Unlocked (Open). Control