36 | Maintenance and service
C 1210 ES/ESC6 720 644 887 (2014/11)
After following instructions indicated in “Troubleshooting” section,
press reset button firmly in order to return heater to normal
operation.
Fig. 61 Reset button
If the problem persists, contact your installer.
6.8 Program button
Fig. 62 “Program” key
6.8.1 Memorizing selected temperature
Press buttons or to select desired temperature.
Hold “Program” button for 3 seconds to save temperature.
When LCD stops blinking, temperature is saved in memory.
Using “Program” function
In order to select memorized temperature
Press “Program” key.
LCD shows pre-memorized temperature, which is now the hot water
selected temperature.
6.9 Locked condition
This condition is only valid for appliances with one or more remote
controls installed.
Fig. 63 Locked condition
Whenever LCD shows , the temperature setting cannot be
adjusted because the appliance is in use by a user which already
selected a different temperature. Appliance will be automatically unlock
5 minutes after closing hot water tap.
7 Maintenance and service
7.1 Annual maintenance
(To remove front cover, see page 8.)
Venting System
Venting system - inspect inside of flue pipe for any blockage or
restriction. Observe burner flames during heater operation. (front
cover must be removed). Burner flames should be steady and blue.
Yellow, inconsistent (bouncing) flames may be an indication of poor
ventilation or combustion air supply. Inspect the combustion air inlet
pipe for blockage or debris. Inspect combustion air and exhaust
terminations for blockage or debris.
Combustion Chamber
Inspect burner observation window (Fig.76, #14) for cracks or
spillage of flue gases. Observe burner flames during heater
operation. Flames should be steady and blue with no signs of
yellowing. Yellow burner flames are an indication of improper
combustion. Refer to Section4.4, page 23, chapter 4.3, page 11 of
this manual to verify exhaust system and combustion air supply
meets manufacturer's specifications.
Pressure Relief
Manually open the pressure relief valve to ensure proper operation.
Inlet Water Filter
Verify the inlet filter screen is clean and undamaged. The inlet water
filter is located on the bottom of the appliance, to the right of the cold
water inlet fitting. (See Fig.32, page 28). Close installer supplied
water shutoff and remove wireform spring clip from filter. Remove
filter, clean and or replace if damaged.
Descaling
In areas where the water supply has a high mineral content, the heat
exchanger should be flushed with a descaling solution. Scale build up
will shorten the life of the water heater and damage resulting from
scale is not covered under warranty. Refer to section7.3 for detailed
+
WARNING:
Always shut off the electrical power supply, shut off
the manual gas valve and shut off the water valves
whenever servicing.
NOTICE:
Check and clean the complete water heating system
once a year.
Carry out a maintenance overhaul if necessary.
Immediately repair defects to avoid damage to the
system.
Annual maintenance table
Every year
1. Inspect venting system X
2. Inspect combustion chamber X
3. Inspect burner X
4. Inspect pressure relief X
5. Inspect water filter X
6.
Inspect Heat
Exchanger
Descaling X
Fin Coils X
7. Inspect condensate trap X
Table 33 Annual maintenance