Bosch EHP 6-11 LW Installation Guide Page 75

  • Download
  • Add to my manuals
  • Print
  • Page
    / 80
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 74
75
TECHNICAL INFORMATION
Technical information
Technical information for three-phase models
Compress 3000 14 LW 17 LW
Emitted/ Supplied output at 0/35°C
1
kW 14.4/3.1 16.7/3.7
Emitted/ Supplied output at 0/50°C
2
kW 13.9/4.2 16.2/4.9
Minimum fl ow heating side l/s 0.35 0.40
Nominal fl ow heating side l/s 0.50 0.57
Maximum pressure available heating side (at nominal fl ow) kPa 54 51
Nominal fl ow of antifreeze mixture to the collector hose l/s 0.78 0.90
Maximum pressure available to collector hose (at nominal fl ow) kPa 74 71
Type of antifreeze
Bioethanol - water or Propylene/ethylene
glycol - water
Maximum pressure heating side bar 1.5
Maximum pressure on collector hose side bar 4
Maximum output temperature to the heating system °C 65
Working temperatures on collector hose side °C -5 to +20
Integrated collector hose and heat carrier pump Yes
Power supply 400V 3N~ 50Hz
Additional heat settings kW 3.0 / 6.0 / 9.0
The recommended type of fuse depends on the electrical output
3
6 kW electric cassette
9 kW electric cassette
A20 25
A25 32
Starting current
4
A52 50
Compressor Scroll
Type R407c HFC refrigerant kg 2.30 2.30
Connection for heat fl uid out/in mm Cu 28 Cu 28
Out/in collector hose connection mm Cu 35 Cu 35
Dimensions of model LW (LxDxH) mm 600x600x1520
Weight of model LW kg 190 195
Control unit Rego 637
1
Output data at 0/35°C and maccord. to clockeating medium fl ow are stated according to the European standard EN 255.
2
Output data at 0/50°C and maccord. to clockeating medium fl ow are stated according to the European standard EN 255.
3
aM type fuse, D curve circuit breaker
4
Soft starter
5
Electric anode included
Page view 74
1 2 ... 70 71 72 73 74 75 76 77 78 79 80

Comments to this Manuals

No comments