2.0 Overview
With a D279A, you can arm and disarm a single zone or point of a Bosch Computer Systems Control/Communicator panel
separately from the rest of the system. The Independent Zone Control (IZC) features a user-programmable four-digit
passcode for arming and disarming, and a built-in panic function. Entry and exit delay times allow you to locate the D279A
Command Center inside the protected area. If you program the D7112, D8112, D9112, D9112B, D7212B and 9000 Series for
opening and closing reports, the D279A can initiate opening and closing reports by zone or point. A 10-wire cable is shipped
with the D279A for interfacing the Independent Zone Control with the panel (4-wires), protective loops (3-wires) and
onboard relay (3-wires).
The D279A is not supervised from the panel: UL Listed applications require arming device supervision. Use the D268/D269
Independent Zone Control to meet the UL requirement for arming device supervision.
2.1 Specifications
2.2 Features
Permits independent arming and disarming of a single control/communicator zone or point
4-digit, user-programmable combination
Built-in panic function
Pre-programmed entry and exit delay times
Individual annunciation of delayed and instant loop status
Panic and burglary alarm signals to control/communicator
Form C relay activation on alarm
Keypad backlights when number keys or the command bar are pressed
Plug-in cable included for simple wiring to the control/communicator
Low-profile surface mount enclosure
Overview
Operating Voltage
Nominal 12 VDC
Current Requirements
Keypad idle: 60 mA
Keypad lit, buzzer on, both loops faulted, and relay
activated: 104 mA
Auxiliary Relay Rating
Form C contacts, 12 VDC, 2 A max.
Dimensions (H x W x D)
4.6 in. x 8.2 in. x 0.816 in. (117 mm x 208 mm x 21 mm)
Wiring
A 10-wire quick-connect plug-in cable is provided for
interfacing the D279A with the Control/Communicator
and the protective loops. 22 AWG (1.2 mm) or heavier
gauge wire is required to connect the loops and
control/communicator to the ten flying leads.
Operating Temperature
+32°F to +122°F (0°C to +50°C)
Non-Condensing Relative Humidity
5% to 85% at +86°F (+30°C)