Page 10 from 63 6720649497 SM HP270-1 2012/09 en 2.2 Electrical Resistance and Thermostat A thermostat control ac
Page 11 from 63 6720649497 SM HP270-1 2012/09 en Pict.15 – Check continuity between terminal
Page 12 from 63 6720649497 SM HP270-1 2012/09 en 2.3 Coil for external source of energy The coil integrated in the
Page 13 from 63 6720649497 SM HP270-1 2012/09 en Components checking procedure Unit o Inspect all the elements
Page 14 from 63 6720649497 SM HP270-1 2012/09 en The list of available material (separate document) must be checked
Page 15 from 63 6720649497 SM HP270-1 2012/09 en The compressor and condenser are needed to enable the same refrige
Page 16 from 63 6720649497 SM HP270-1 2012/09 en Model - 10ºC to +35ºC The working principle of this model is the
Page 17 from 63 6720649497 SM HP270-1 2012/09 en 3.3 Main Components Data Evaporator Suppliers: Behr, Mahle S
Page 18 from 63 6720649497 SM HP270-1 2012/09 en Dry filter Supplier: Honeywell (Series FF) Specifications f
Page 19 from 63 6720649497 SM HP270-1 2012/09 en 3.4 Electrical Measurements Pi
Page 2 from 63 6720649497 SM HP270-1 2012/09 en 1. INTRODUCTION ...
Page 20 from 63 6720649497 SM HP270-1 2012/09 en Position (Scheme Nr) Model +5ºC / +35ºC Model -10ºC / +35ºC Compon
Page 21 from 63 6720649497 SM HP270-1 2012/09 en The NTC’s listed in the table above, are supplied in a common cabl
Page 22 from 63 6720649497 SM HP270-1 2012/09 en 55 2957 2986 60 2521 2488 65 2157 2083 70 1853 1752 75 1598 1481 8
Page 23 from 63 6720649497 SM HP270-1 2012/09 en 4. Components Overview 4.1 Compressor The compressor is usually
Page 24 from 63 6720649497 SM HP270-1 2012/09 en Electric test to the compressor: The compressor has some electri
Page 25 from 63 6720649497 SM HP270-1 2012/09 en Electric test to compressor: Check earth connection C – chassis ≠
Page 26 from 63 6720649497 SM HP270-1 2012/09 en (a) Open contact
Page 27 from 63 6720649497 SM HP270-1 2012/09 en 4.2 Filters and driers Moisture or water vapour may cause problem
Page 28 from 63 6720649497 SM HP270-1 2012/09 en evaporation cooling. In order to achieve optimum cooling capacity
Page 29 from 63 6720649497 SM HP270-1 2012/09 en Pict.38 – Pressure switch from Danfoss Various shunt relays
Page 3 from 63 6720649497 SM HP270-1 2012/09 en 1. Introduction Domestic Hot Water Heat Pumps (DHW-HP), with
Page 30 from 63 6720649497 SM HP270-1 2012/09 en Pict.40 – Fan and Evaporator 4.6 Condenser Pict.41 – Condenser
Page 31 from 63 6720649497 SM HP270-1 2012/09 en Pict.42 – Plate heat exchanger condenser working principle In cas
Page 32 from 63 6720649497 SM HP270-1 2012/09 en Pict.44 – HMI Panel Entrance in the service mode: Press “Me
Page 33 from 63 6720649497 SM HP270-1 2012/09 en X X 6d Number of air defrost procedures + X 7d Number
Page 34 from 63 6720649497 SM HP270-1 2012/09 en The working principle is based in the following considerations:
Page 35 from 63 6720649497 SM HP270-1 2012/09 en Conditions for operation: The heat pump compressor is activated a
Page 36 from 63 6720649497 SM HP270-1 2012/09 en Conditions for air-defrost sequence: Air defrost sequence
Page 37 from 63 6720649497 SM HP270-1 2012/09 en 6. Maintenance and preventive actions 6.1 Corrosion Corrosion i
Page 38 from 63 6720649497 SM HP270-1 2012/09 en The corrosive effect of natural water can vary considerably with i
Page 39 from 63 6720649497 SM HP270-1 2012/09 en > 300 0 0 / + Free chlorine (Cl2) < 1 + + 1 – 5 + 0 &g
Page 4 from 63 6720649497 SM HP270-1 2012/09 en 1.1 General description This model of domestic hot water heat pump
Page 40 from 63 6720649497 SM HP270-1 2012/09 en o pH o calcium content o alkalinity o ionic strength of the wa
Page 41 from 63 6720649497 SM HP270-1 2012/09 en Cables Check position*, connection, continuity * Ensure distance
Page 42 from 63 6720649497 SM HP270-1 2012/09 en In the NTC sensor, in contact with the pipe of cold water from th
Page 43 from 63 6720649497 SM HP270-1 2012/09 en Pict.49 – Kaloxi descaling liquid to clean plate heat exchangers
Page 44 from 63 6720649497 SM HP270-1 2012/09 en Pict.51 – Flexible hose of descaling pump connection - Put the p
Page 45 from 63 6720649497 SM HP270-1 2012/09 en Pict.53 – Example of a manual air purge Evaporator Maintenance T
Page 46 from 63 6720649497 SM HP270-1 2012/09 en Pict.56 – Example of cleaning and purifier spray for evaporators
Page 47 from 63 6720649497 SM HP270-1 2012/09 en 7. Troubleshooting Code E01 Lock Out error Fault in the hot wat
Page 48 from 63 6720649497 SM HP270-1 2012/09 en Code E07 – Only for internal technical use Code E08 – Only for int
Page 49 from 63 6720649497 SM HP270-1 2012/09 en 2 Contacts Open on safety elements – high pressure switch Check
Page 5 from 63 6720649497 SM HP270-1 2012/09 en 1.2 Product presentation Apart of the main function of the heat p
Page 50 from 63 6720649497 SM HP270-1 2012/09 en 7.1 Failures prevention and detection The design data supplied by
Page 51 from 63 6720649497 SM HP270-1 2012/09 en 7.2 Evaporator under performance The evaporation process is sens
Page 52 from 63 6720649497 SM HP270-1 2012/09 en Pict.59 – Position of the bulb and insulation 7.3 Condenser u
Page 53 from 63 6720649497 SM HP270-1 2012/09 en 7.4 Other recommendations and definitions Pict.60 – General refr
Page 54 from 63 6720649497 SM HP270-1 2012/09 en 7.5 Service Needs Using pressure manometers and thermometer The
Page 55 from 63 6720649497 SM HP270-1 2012/09 en During the process of repairs and manometer connections to the pre
Page 56 from 63 6720649497 SM HP270-1 2012/09 en Efficiency Definition The basic compressor-driven refrigeration c
Page 57 from 63 6720649497 SM HP270-1 2012/09 en In the ideal cooling circuit the superheat is 0°C. This means tha
Page 58 from 63 6720649497 SM HP270-1 2012/09 en Pict.66 – Expansion valve and bulb position Sub
Page 59 from 63 6720649497 SM HP270-1 2012/09 en 8. Appendix Guide with list of material for service partners Th
Page 6 from 63 6720649497 SM HP270-1 2012/09 en 1.3 Working principle The heat pump working principle is based on
Page 60 from 63 6720649497 SM HP270-1 2012/09 en Soldering equipment To soldering components in repairs in the
Page 61 from 63 6720649497 SM HP270-1 2012/09 en Recovery Equipment To use during phase out of the gas to deli
Page 62 from 63 6720649497 SM HP270-1 2012/09 en Brush / cleaning tools Inner and outer cleaning and finishin
Page 63 from 63 6720649497 SM HP270-1 2012/09 en Table 10 – List of material for safety, handling and repairs Bos
Page 7 from 63 6720649497 SM HP270-1 2012/09 en 2. Heat Pump Elements The top EPP cover must be carefully disass
Page 8 from 63 6720649497 SM HP270-1 2012/09 en 2.1 Anode Protection The anode, installed in the water heater tan
Page 9 from 63 6720649497 SM HP270-1 2012/09 en An anodic current meter can be used to measure the current and eva