Alarm relay follows manual alarm
Press zone key 5.
This takes you to the Output Config menu.
Press zone key 2.
This takes you to the Alarm Relay submenu.
Press zone key 2.
This takes you to the Drillable submenu.
Press zone keys 1 or 2.
1 Drillable
2= Not Drillable (default setting)
OC/Relay Extensions
In the OC/Relay Ext menu, you can individually set the
properties of all OC/Relay outputs. The possible settings for the
OC/Relay outputs 2 to 8 correspond to those for the first OC/
Relay . The following settings are possible:
– Zone = Alarm: The output is activated if the zone triggers
an alarm. Here zone 1 is assigned to output 1, etc.
– Zone Normal: If the zone is not in a normal state, the
output is activated. Assignment: zone 1 to output 1 etc.
– Sum Alarm: When the fire panel is in an alarm state, this
output is activated regardless of the zone.
– Sum PreAlarm: When the fire panel is in a pre-alarm state,
this output is activated regardless of the zone.
– Sum Fault: This output is activated if there is a fault.
– Sum Disable: If a fire panel element is disabled, this output
is activated (zones, notification appliances, relays).
– Sum Test: This output is activated if a zone in the fire panel
is in test mode.
– Not Used: The output is not used.
4.5.3
52 en | System Configuration Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH