Bosch FPC-500-8 Installation Guide Page 61

  • Download
  • Add to my manuals
  • Print
  • Page
    / 82
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 60
Communication parameters
FPC-500
‑2
FPC-500
‑4
FPC-500
-8
Notification appliances
Standby
A-
B+
Alarm state
A-
B+
10 V to 15 V
0 V to 0.5 V
0 V to 1 V
21 V to 29 V
Inputs
Alarm resistor 820 ohm ±5%
EOL Resistor 3900 ohm ±1%
Zones (with resistance combination)
Alarm resistor 820 ohm ±5%
910 ohm ±5%
No 2-Det Depend: 680 ohm
±5%
EOL Resistor 3900 ohm ±1%
Zones (with EOL modules)
Alarm resistor 820 ohm ±5%
910 ohm ±5%
No 2-Det Depend: 680 ohm
±5%
6.1.1
Conventional Fire Panel Technical Data | en 61
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Page view 60
1 2 ... 56 57 58 59 60 61 62 63 64 65 66 ... 81 82

Comments to this Manuals

No comments