Bosch Security Systems | 2004-06 | 9922 141 10371en
Plena Voice Alarm System | Installation and Operating | Configuration en | 47
5 Configuration
5.1 Introduction
A number of functions within the system are hardware
configurable by DIP switches. However, most functions
are software configurable, using the Configuration
Software.
5.2 Hardware configuration
A complete Plena Voice Alarm System can be hardware
configured using:
The system settings DIP switch (see section 5.3), the
VOX configuration (DIP) switches (see section 5.4.2)
and the master volume control knobs on the rear of
the controller.
The CS configuration DIP switch (see section 5.5) on
the bottom of each call station.
The ID rotary switch and the termination switch on
the rear of each router (see section 5.6).
5.3 System settings DIP switch
The system settings are configured using the system
settings DIP switch on the rear of the controller (see
figure 5.1). By default, all switches are in the OFF
position.
5.3.1 Monitor
If the Monitor switch (see figure 5.1) is in the ON
position, the internal monitoring loudspeaker of the
controller is switched on. The volume of the monitoring
loudspeaker is set with the Monitoring Speaker master
volume control knob (see figure 2.3, no. 35).
5.3.2 APR mode
If the APR mode switch (see figure 5.1) is in the ON
position, the system operates in the Asian-Pacific
Region (APR) mode. In APR mode, the system operates
according to the emergency standards of the Asian-
Pacific Region.
5.3.3 Supervision
If the Supervision switch (see figure 5.1) is in the ON
position, supervision is enabled. If it is in the OFF
position, supervision is disabled. To indicate that
supervision is disabled, the Disabled indicator on the
front panel of the controller is turned ON (see figure
5.2). For an overview of all functions that can be
supervised, see 5.3.3.1.
Note
Refer to the Configuration Software Manual
(9922 141 10381) for details about using the
software.
figure 5.1: System settings DIP switch
Monitor
APR mode
Supervision
2ch operation
LBB1994
Off
On
table 5.1: System settings DIP switch settings
DIP switch Description
Monitor Switches the monitoring
loudspeaker on (ON) or off (OFF).
See section 5.3.1.
APR mode Switches the Asian Pacific Region
mode on (ON) or off (OFF). See
section 5.3.2.
Supervision Switches supervision on (ON) or off
(OFF). See section 5.3.3.
2ch operation Switches 2-channel operation on
(ON) or off (OFF). See section 5.3.4.
LBB1994 For future use. This switch must
always be in the OFF position.
figure 5.2: Supervision: Disabled indicator
Processor reset
Network
Call/EMG
Music/Spare
Ground short
Input
Mains
Battery
Zone1
Zone2
Zone3
Zone4
Zone5
Zone6
Fault Indicators
A
B
Disabled
Message
EMG mic
RCP
Router
0dB
-6dB
-20dB