14 en | Setting Up Points and Outputs GV3 Series v8.11 or Higher
F01U170805 | 02 | 2011.10 Quick Reference Guide Bosch Security Systems, Inc.
6.2 Point Index (Default Values)
Table 6.3 Point Index Numbers and Descriptions
To make a custom Point Index, refer to (Table 6.4 and Table 6.5).
Table 6.4 Point Type Selections
Pt Index
Number
Description Pt Index
Number
Description
1 24-Hour Instant Audible Alarm on Open or
Short
17 D279 (Non-Priority)
2 Invisible/Silent Hold Up on Short 18 D279 (Priority)
3 Fire Pull Station Alarm on Short 19 Easikey Input
4 Smoke Detector with Reset Alarm on Short 20 POPIT Motion Sensor Interior
5 Smoke Detector with Verification Reset and
Alarm on Short
21 POPIT Motion Sensor Perimeter
6 Bell Supervision Trouble on Open/Short 22 Fire Supervisory on Open, Trouble on Short
7 Perimeter Instant Alarm on Open or Short,
Watch Point when Disarmed
23 Non-Fire Supervisory on Open, Trouble on
Short
8 Perimeter Delay on Short, Instant Alarm on
Short, Watch Point when Disarmed
24 Local, No Visual or Audible Display on Any Fault
Armed or Disarmed with Relay Output
9 Perimeter Instant Alarm on Open or Short,
Local while Disarmed
25 Perimeter Delay on Open, Alarm on Short
10 Interior Instant Alarm on Open or Short 26 24-Hour Instant Audible Alarm on Open or
Short
11 Interior Delay on Short, Alarm on Open 27 24-Hour Instant Audible Alarm on Open or
Short
12 Interior Instant Alarm on Open or Short, Local
while Disarmed
28 24-Hour Instant Audible Alarm on Open or
Short
13 Interior Follower Delay on Short, Alarm on
Open
29 24-Hour Instant Audible Alarm on Open or
Short
14 Maintained Keyswitch 30 24-Hour Instant Audible Alarm on Open or
Short
15 Momentary Keyswitch 31 24-Hour Instant Audible Alarm on Open or
Short
16 Open/Close on Fault
NOTICE!
The default indexes are not always the best selection.
If you experience unwanted trouble conditions, refer to Table 6.5 on Page 15 and make any
necessary adjustments.
Bosch Commercial Wireless points produce a Short when faulted and an Open for a tamper.
Pt Type Description Pt Type Description
0 24-Hour 6 O/C/ Port
1 Perimeter 7 D279 (O/C Non-Priority)
2 Interior 8 D279 (Priority)
3 Interior Follower 9 Easikey
4 Keyswitch 11 AUX AC Supervision
5 Keyswitch Memory