Bosch Security Systems | 2005-01 | 9922 141 10363en
Plena Voice Alarm System | Basic System Manual | Important Notices en | 4
Important Notices
When using routers, keypads or more than one call
station, configure the controller using the supplied
software.
Use shielded cable (Cat-5) between the routers and the
controller.
The factory default setting of the Plena Voice Alarm
Controller is as follows:
• Stand-alone unit configured for an ISO 60849
compliant system when used with a spare power
amplifier from the Plena range and compliant wiring
and loudspeakers.
• One channel system.
• Supervision on for:
• Loudspeaker lines
(90 seconds interval, 15% accuracy)
• Main and spare power amplifier
• Short to ground (“Ground short”)
• Mains and battery power
•EMG mic
•Memory
Please note that when used with the factory default
configuration:
• The background music (BGM) is muted when no
spare power amplifier is connected. Disabling the
spare power amplifier supervision or overall
supervision restores the BGM.
• The BGM will not be present in non-selected zones
during a call. If this is desired, connect a spare/call
power amplifier and switch the system to 2-channel
mode.