18 en | Installation NurseCall N46 Wall Transmitter
970.030 | v1.0 | 2009.06 User Manual Bosch Security Systems
5.3 Inputs and Outputs
5.4 General inputs
The * marks a factory setting.
5.5 Wired Outputs
5.6 Wired Inputs
External trigger J4 Jack 3.5 mm J1 NO* Closing contact causes a Call for Help
NC
Contact opening causes a Call for Help
Power supply J5 1 + 12 to 24 V DC
2
-
GND 0V
Call for Help
Relay
J5 3-4 B1 NO* A Call for Help causes the closing of
the relay contact
NC A Call for Help causes the opening of
the relay contact
Staff Presence
Relay
J5 5-6 B2 NO* Staff Presence signaling causes the
closing of the relay
NC Staff Presence signaling causes the
opening of the relay
Call for Help J6 1-2 The contact closing causes a Call for
Help.
Technical
Alarm
J6 3-4 J2 NO* The contact closing causes a Technical
Alarm
NC The contact closing causes a Technical
Alarm
Call for Help 2
or Call for
Assistance
J6 4-5 J3 NO* The contact closing causes a Call for
Help 2 or a Call for Assistance
NC The contact opening causes a Call for
Help 2 or a Call for Assistance