Relay Unit Operation | en 23
Bosch Security Systems User Manual F.01U.278.516 | V1.0 | 2012.11
Third information block
8. position of the last passed beacon, visible in all display modes. If no beacon is registered
or if the alarm is sent outside of the range of a beacon, the POS 000 will be displayed.
In the alarm buffer, the total number of entries is indicated on top at the right. You can
immediately see how many alarms are active. In this example, there are a total of three alarms
in the alarm buffer. In the event buffer, the position of the event in the buffer is indicated:
Here, E01 corresponds to the latest entry in the event buffer.
Unit displaying the current date and time:
Unit displaying an active alarm:
Unit displaying an event in the buffer:
5.2.3 The green button does not work
Problem: you have tried unsuccessfully to acknowledge an alarm with the Green button.
Cause: the local acknowledgement is disabled.
Solution: activate the local acknowledgement function.
See the Main Unit user manual.
5.2.4 Disconnecting a Relay Unit
If a Relay Unit stops communicating with the Main Unit, an alarm "Relay Off" is generated on
the Main Unit. This alarm can only be acknowledged on the Main Unit by pressing the Green
button, followed by the code 45. Thereafter, an event "No Relay" is generated.
As soon as the Relay Unit communicates again with the Main Unit, the Event "Relay On" is
generated. This operation is independent of the local acknowledgement setting.
LOCAL ACK. E01
06:05:11 13:33:05 C2
DATE: 03.01.11 ¨
TIME: 12:12:31
HELP A01
NU:001
LOCAL ACK. E04
NU:001