34 | Electrical SM Series Heat Pump
SM Series Heat Pump6 720 220 406 (2013/1) Subject to change without prior notice
When the switch is set for Hot gas re-heat -" YES"
the unit will energize the H output on P13 when
sensing a 24 VAC input on the TB01-H. This will in
terms activate the re-heat coil for active de-
humidification.
When the switch is set to Hot gas re-heat - "NO".
the unit will disable the H terminal on P13 at all
times, when sensing a 24VAC signal on TB01-H the
unit will run the blower motor at a lower CFM in
order to have a passive dehumidification while
cooling the space.
The other DIP switch bank is used to select the
proper program in the ECM motor for the unit.
To the left of the red and green status LED’s is a
row of 1/4” male quick connects. These are used
to pass thermostat inputs on to the rest of the
control circuit. Remember to always turn off unit
power at the circuit breaker before attaching or
disconnecting any wiring from these connections
to avoid accidental short circuits that can damage
unit control components.
Do not set the ADJ DIP switch to the (-)
setting when electric heaters are installed.
Doing so may cause the heaters to cycle on
their thermal overload switches, potentially
shortening the life of the switches.
Always disconnect power before changing
jumper positions on the interface board and
reset the unit afterward.