troubleshooting | 51SM Series Heat Pump
6 720 220 406 (2013/1)SM Series Heat Pump
YELLOW "ALERT”
FLASH CODE 6
Open Start Circuit
Current only in run
circuit
1. Run capacitor has failed (may not be bad, verify)
2. Open circuit in compressor start wiring or connections
Check wiring and connectors between supply and
the compressor "S'" terminal
3. Compressor start winding is damaged
Check compressor motor winding resistance
YELLOW "ALERT”
FLASH CODE 7
Open Run Circuit
Current only in start
circuit
1. Open circuit in compressor run wiring or connections
Check wiring and connectors between supply and
the compressor "R” terminal
2. Compressor run winding is damaged
Check compressor motor winding resistance
YELLOW "ALERT"
FLASH CODE 8
Welded Contactor
Compressor always
runs
1. Compressor contactor has failed closed
2. Thermostat demand signal not connected to module
YELLOW "ALERT"
FLASH CODE 9
Low Voltage
Control circuit <
17VAC
1. Control circuit transformer is overloaded
2. Low line voltage (contact utility if voltage at disconnect
is low)
Check wiring connections Flash Code number
corresponds to a number of LED flashes, followed
by a pause and then repeated. TRIP and ALERT LEDs
flashing at same time means control circuit voltage
is too low for operation
Comfort Alert Module -Flash Codes
Status LED
Status LED
Description Status LED Troubleshooting Information Solution
HRP Troubleshooting
Problem Possible Cause Checks and Corrections
NO FLOW
LOW FLOW
No Power Check power supply
On/Off Switch Position Set switch to “ON” position
Compressor Contactor Engage heat pump contactor
Broken or loose wires Repair or tighten wires
Air Lock Purge air from piping system
Stuck pump shaft/impeller Remove pump cartridge and clean
Defective pump Replace pump
Kinked or under sized water piping Repair kink and check for proper line size
HIGH WATER
TEMPERATURE
Water temp limit closed Stuck limit switch
Sensor not attached securely to line
LOW HEAT OUTPUT Scaled or fouled heat exchanger Clean heat exchanger