Fire System | User’s Guide | 11.0 System Functions
Bosch Security Systems, Inc. | 8/06 | F01U011793B 27
11.2.2 FIRE TEST ?
Description
Use this function to test fire points to be certain they function
properly. You can review untested points at your keypad to
help locate the remaining detectors to be tested.
Upon initiation, the fire test will test the fire pattern on the
alarm output and ring the keypad sounder for two seconds.
The AC power is disabled for four minutes to test the
system’s battery power. If the battery cannot maintain the
system for the four-minute period, the keypad appears to be
not functioning. If this happens, contact your servicing
company. At the end of the four-minute period, AC power
returns to the system and the control panel restores. A
message is sent to your monitoring facility upon initiation and
completion of the Fire Test. During the Fire Test, no alarms
are sent to your monitoring facility.
If the system has no activity for 20 minutes, the system
automatically exits from the Fire Test.
Using the Fire Test
1. Press the [ESC] key to enter the menu, then press
[NEXT] repeatedly until you reach the FIRE TEST ?
prompt. Press [ENT].
2. ## PTS TO TEST appears in the display.
3. One at a time, activate the detection devices to fault each
point.
4. As you fault each point, your keypad displays the point
text for 60 seconds and the bell sounds for two seconds.
This verifies that the detection device is working
properly. Your system automatically resets smoke
detectors.
When a resettable point (such as a smoke detector) is
faulted, the display shows SENSOR RESETTING for five
seconds. During this time power is removed from smoke
power relays.