GV2 Series Control Panels | Owner's Manual Supplement
10 Bosch Security Systems, Inc. | 2/07 | F01U063791-01
2.6 Walk Tests
2.6.1 Description
The D9412GV2, D7412GV2, and D7212GV2 have three Walk Test
menus that allow the user to test various points that are within
the scope of the keypad without sending a report to the central
station.
Test each smoke detector according to the manufacturer’s
instructions.
Table 1: Walk Test Menu Access
Test Type Command
Sequence
Menu Function Name Point Types
Tested
Walk [COMMAND][4][4]
WALK TEST ?
Visible
Perimeter and
Interior
Fire [COMMAND][5][8]
FIRE TEST ?
Fire and 24-
hour
Invisible Not applicable
INVISIBLE TEST ?
Invisible
Perimeter and
Interior
I have this feature.
I do not have this feature.
2.6.2 Using Walk Test
On a D1255 Keypad:
1. If you use the command sequence, press the keys shown in
the Command Sequence column of Table 1 for the necessary
test. The keypad shows the number of testable points within
the scope of the keypad: ### PTS TO TEST. Proceed to Step
5.
2. If you use menu function list, press the [ESC] key.
3. Press the [NEXT] key until the Menu Function Name (refer to
Table 1) appears.