74-06666-000-B 12/93
© 1993 Radionics
D9112 Installation and Troubleshooting Quick Reference
Page 2
Basic Troubleshooting
Command 5 7 Toggles Default Idle Text
Command 5 7 allows technicians who might not be familiar with the custom idle text to confirm
whether an area is armed, ready to arm, or not ready to arm. The default idle text displays are:
AREA # IS ON AREA # IS OFF
Follow the procedure below to toggle between custom and default idle text.
1. Ensure the command center is at idle text.
2. Press COMMAND 5 7.
3. The display will change to default idle text for 5 seconds and then revert to its original
idle text.
Command 5 9 Shows Firmware Revision
Command 5 9 displays the revision of firmware currently installed in the panel.
1. Ensure the command center is at idle text.
2. Press COMMAND 5 9.
3. The current revision of firmware displays (
9112 REV # # - # #
) for 5 seconds and
returns to idle text.
Service Walk Test Shows Extra Points
The Service Walk Test differs from the standard Walk Test in that POPITs whose switches are
set for a point number not programmed in the panel appear in the test.
Service Walk Test only available at command centers with panel wide scope:
See
Command Center
in the
D9112 Control/Communicator Program Entry Guide
(74-06145-000) for
a description of command center scope.
Warning, fire and other 24-hour points do not transmit reports during Service Walk Test!
The steps below outline a simple Service Walk Test procedure. The flow chart on the next page
shows all the Service Walk Test options.
1. Choose a command center with panel wide scope to conduct the test. Be certain the
display shows the idle disarmed text.
2. Press 9 9 ENT to display the first item in the Service Menu.
3. Press NEXT to step through the menu items until
SERVICE WALK?
appears in the
display.
4. Press ENT.
5.
ENTER PASSCODE
appears in the display if you programmed Service Walk Test
access to be restricted by authority level.
Enter a passcode assigned an authority level with access to the Service Walk Test
function. Press ENT.
6. The display shows
### PTS TO TEST
. Test the first detection device.
7. As you fault the detection devices, the command center emits a brief tone, briefly
displays the point text for the point tested, and returns to the points to test display.
Comments to this Manuals