9.4.4 Setting the OctoPOPIT Switches
The D8128D OctoPOPIT has two sets of DIP
switches (Figure 17 on page 50). Use the DIP
switches on the top of the unit (with the terminal
strip along the left edge) to set the address for
the OctoPOPIT. Use the DIP switches at the
bottom of the unit to enable or disable individual
points connected to the OctoPOPIT.
Address Switches
The switches on the D8128D OctoPOPIT set
point assignments and line termination. These
switches are easier to set before mounting the
D8128D in the enclosure.
Switches 1, 2, 3, and 4 assign the OctoPOPIT
sensor loops to point numbers on the control
panel. Table 15 shows the OctoPOPIT switch
settings for point assignments.
Switch 5 sets line termination. Refer to Table 16:
Switch 5 Settings for Line Termination.
Table 15: D8128D OctoPOPIT Switch Settings
ZONEX 1 D8128D Address Switches ZONEX 2
Points 9 to
127
1 2 3 4 5
Points 129
to 247
9 to 16
ON
ON
ON
ON
*
129 to 136
17 to 24
ON
ON
ON
OFF
*
137 to 144
25 to 32 ON ON OFF ON * 145 to 152
33 to 40
ON
ON
OFF
OFF
*
153 to 160
41 to 48 ON OFF ON ON * 161 to 168
49 to 56
ON
OFF
ON
OFF
*
169 to 176
57 to 64
ON
OFF
OFF
ON
*
177 to 184
65 to 72 ON OFF OFF OFF * 185 to 192
73 to 80
OFF
ON
ON
ON
*
193 to 200
81 to 88 OFF ON ON OFF * 201 to 208
89 to 96
OFF
ON
OFF
ON
*
209 to 216
97 to 104 OFF ON OFF OFF * 217 to 224
105 to 112 OFF OFF ON ON * 225 to 232
113 to 120 OFF OFF ON OFF * 233 to 240
121 to 127
OFF
OFF
OFF
ON
*
241 to 247
* Line Termination Switch
For the D8128D OctoPOPITs assigned to
Points 121 to 127, 241, and 247, set Point
Input Switch 8 to the OPEN position.
D9412
GV4 uses Points 9 to 127 on Zonex
1 and Points 129 to 247 on
Zonex 2.
D7412
GV4 uses Points 9 to 75 on Zonex 1
only.
Table
16: Switch 5 Settings for Line
Termination
Is a D8125 POPEX
Module connected?
Switch 5 Setting(s) on
D8128D OctoPOPIT(s)
No
Set Switch 5 of only one
D8128D to ON
Yes
Set Switch 5 of all
D8128Ds to
OFF
Point DIP Switches
Each point connected to the D8128D is enabled
by closing the respective DIP switch, or disabled
by opening the DIP switch. For example, to
disable a device connected to the P3 Terminal
(Point 3), move DIP switch number 3 to the
OPEN position.
Use the point DIP switches to disable conflicting
points, such as when a D9210C Access Control
Module must be assigned to a point that falls
within the range of the D8128D OctoPOPIT. In
this example, a D9210C is assigned to Point 20.
On the same system, a D8128D OctoPOPIT is
assigned to Points 17 through 24. Moving the DIP
switch for Point 4 to the OFF position would
effectively disable Point 20, allowing normal
operation of the D9210C and the OctoPOPIT.
Through panel configuration the Point Source
prompt further protects from possible point
addressing conflicts. A point can be ZONEX,
Octo-input, SDI2 Wireless, or Door Point.
Terminate each OctoPOPIT sensor loop with a 1 k
Ω EOL resistor. Attach a resistor even if you do
not enable the loop.
9.4.5 Mounting OctoPOPITs
The D8128D OctoPOPIT Module can be installed
in the enclosure with the control panel using
standard four-conductor 22 AWG (0.8 mm) wire,
or in a separate enclosure (Model D8103,
D8103A, or D8109) up to 200 ft (61 m) from the
control panel using shielded (recommended)
standard four-conductor 22 AWG (0.8 mm) wire.
If using the D125B or D129, refer to the
Specifications section of the D8128D Installation
Guide (P/N: F01U070537) for cabling
requirements.
For UL Listed systems, mount the D8128D in a
tamper-proof enclosure. To install OctoPOPITs in
the control panel’s enclosure, complete the
following procedure. Use the D137 Mounting
Bracket to install OctoPOPITs in enclosures with
no module-mounting locations available.