The flue system must be installed following the requirements of
BS5440:1.
The standard flue kit length is 425 - 725mm. Extension kits for
flues up to 4m are available.
The terminal must not cause an obstruction nor the combustion
products a nuisance.
If the terminal is within 1m of a plastic or painted gutter or
within 500mm of painted eaves then an aluminium shield at
least 750mm long should be fitted to the underside of the gutter
or painted surface.
If the terminal is less than 2m above a surface to which people
have access then a guard must be fitted. The guard must be
evenly spaced about the terminal and fixed with plated screws.
A guard Type K2 can be obtained from Tower Flue Components,
Vale Rise, Tonbridge, TN9 1TB.
It is essential that products of combustion cannot re-enter the
building. Refer to Fig 4.
A separate vent for combustion air is not required.
If the appliance is in a cupboard or compartment it is not
necessary to have additional ventilation for the boiler
providing that the following clearances are provided:
* Clearance to a removable panel i.e. door.
If the appliance is installed in a cupboard or compartment that
does not allow these clearances then permanent air vents are
required in the compartment, one at a high level and one at a
low level. Both high and low level air vents must communicate
with the same room or must both be on the same wall to the
outside air. The minimum requirements are:
6. Air Supply5. Flue terminal positions
7
L
L
K
K
F
F
G
A
M
EJF
HI
D
G
A
B,C
Fig. 4. Siting of the flue terminal.
TERMINAL POSITION MIN. DISTANCE TERMINAL POSITION MIN. DISTANCE
A– directly below an openable window or I– From a terminal facing a terminal 1200mm
other opening e.g. air brick. 300mm J– From an opening in a car port (e.g. door
B– Below gutters, soil pipes or drain pipes. 75mm window) into dwelling. 1200mm
C– Below eaves. 25mm K– Vertically from a terminal on the same
D– Below balconies or car port roof. 25mm wall. 1500mm
E– From vertical drain pipes and soil pipes. 25mm L– Horizontally from a terminal on the same
F– From internal or external corners. 25mm wall. 300mm
G– Above ground, roof or balcony level. 300mm M– From door, window or air vent (achieve
H– From a surface facing a terminal. 600mm where possible). 300mm
Above the flue turret 30mm
In front* 250 mm
Below 200mm
Right-hand side 75 mm
Left-hand side 75mm
Model Position of vent Air from room Air from outside
24SBi High 315cm
2
158cm
2
Low 315cm
2
158cm
2
15SBi High 315cm
2
158cm
2
Low 315cm
2
158cm
2