48 | Heatronic settings
6 720 644 143 (2010/09)
Service function 4.F: Siphon-fill programme
The syphon filling function ensures that the syphon trap
is filled when the appliance is first installed or shut down
for a long period. Flue gas is prevented from escaping
into the room where the appliance is installed.
The trap filling function is activated when:
the appliance is switched on at the main switch
the burner has not been in use for at least 48 hours
the appliance is switched from summer to winter
mode
The next time the heating or hot water system calls for
heat, the appliance is held at minimum output for
15 minutes.
The syphon filling programme remains active until the
appliance has completed 15 minutes of operation at
minimum output.
The 2-digit display alternates between and the CH
flow temperature.
Service function 5.A: Reset service reminder
The burner service interval of 2324 hours has run out.
After the service inspection store 0 for resetting the
service interval.
Service function 5.b: Fan over-run time
B Set the time of fan over-run after a boiler demand.
Service function 6.A: Last fault
The last fault can also be recalled for servicing purposes
when the appliance is functioning correctly.
Service function 6.d: Current turbine flow rate (ZWB
only)
The actual flow rate of the turbine is displayed.
Service function 6.E: Programmer input
Shows the status of channel 1 of the timer DT10/20. Left
digit is “Heat demand”, heating mode will be activated
according to the programmer commands. Shows the
status of channel 2 of the timer DT20. Right digit is
“DHW demand”, hot water mode will be activated
according to the programmer commands.
Service function 7.A: Fault indicator LED ON/OFF
The fault indicator LED flashes in case of error even
when its setting is off (0).
DANGER: If the syphon is not filled, flue gas
can escape.
B Only deactivate the syphon filling
programme in order to carry out servicing
work.
B Always re-activate trap filling programme
once servicing is complete.