D7212GV3 | Operation and Installation Guide | 13.0 Programmer Connections
50 Bosch Security Systems, Inc. | 10/10 | F01U143079-03
13.2 Installer Keypad and Local
Programmers Mode
While installing or maintaining a D7212GV3 control
panel, it is sometimes necessary to change the
configuration. To do so, a local keypad programming
menu is available in the Service Menu. You can
access the Service Menu when the control panel is in
stand-by mode or while it is operating. Refer to the
D7212GV3 Control Panel Program Entry Guide
(P/N: F01U170808) for an explanation of the
programming menu.
Accessing Local Keypad Programming when the
Control Panel is Operating (Reset Switch Open)
To access the Local Programmers Menu while the
control panel is operating:
1. Disarm all areas in the control panel.
Local keypad programming is only accessible
when all areas are disarmed.
2. At any D1255 or D1260 Keypad, press
[9][9][ENTER] to access the Service Menu.
3. Enter the Service passcode when prompted.
4. Advance the menu to the Keypad Programming
option, then press [ENTER] to enter programming
mode.
The Keypad Programming menu is only available
when all areas in the control panel are disarmed.
Accessing Local Keypad Programming when the
Control Panel is in Standby Mode (Reset Switch
Closed)
The control panel is in standby mode when the Reset
pin is closed. Refer to Figure 23 on page 49. While
the control panel is in standby mode, you can access
the Service Menu at one of two keypads with the
following restrictions:
An unsupervised D1260 Keypad (all versions)
at SDI Bus Address 8.
The D1260 Keypad does not support SDI Bus
Address 16.
An unsupervised D1255 Keypad (all versions)
at SDI Bus Address 16.
If a D1255 is set to SDI Bus Address 8, then
that keypad cannot be used to access the
Service Menu.
Only one keypad at a time is allowed to be in
use.
To access Local Keypad Programming when the
control panel is in standby mode:
1. From the keypad (D1260 at SDI Address 8 or
D1255 ad SDI Address 16), enter the Service
Passcode.
2. Advance the menu to the Keypad Programming
option.
3. Press [ENTER] to enter Local Keypad
Programming.
13.3 Programmer Access Reports
When a program is sent to the control panel from
RPS, the control panel sends a Prog Access OK.
The prompt in routing must be programmed Yes to
send this report.
If the control panel is configured with the Reset switch
closed, then this report is deferred until after the
switch is unlocked.
Page view 49