GV2 Series Control Panels | Owner's Manual Supplement
Bosch Security Systems, Inc. | 2/07 | F01U063791-01 23
3.3 User-Caused False Alarms, Arming the System
3.3.1 Exit Time Defaults
The SIA standard calls for Exit Time to range from 45 sec to at
least two min (not to exceed 255 sec).
The default is 60 sec.
3.3.2 Exit Tone
The SIA standard requires that the control panel provide an Exit
Tone to alert anyone remaining in the premises that Exit Delay is
in process. The tone pulsing rate increases during the last 10 sec
of Exit Time.
The Exit Tone can be disabled only for individual keypads, not for
the entire system.
During the last 10 sec of Exit Delay, the control panel’s Alarm Bell
output pulses on and off for the last 10 sec of Exit Delay.
3.3.3 Exit Time Restart
The SIA standard requires that the control have an option that
restarts Exit Delay if a user follows these steps:
1. Starts Exit Delay (arms the system)
2. Exits and closes an Exit Delay zone.
3. Returns through an Exit Delay zone.
4. The control panel restarts Exit Delay (one-time restart only).
I have this feature.
I do not have this feature.
3.3.4 Exit Error
When a user leaves an Exit Delay zone faulted at the end of Exit
Time, the control panel creates an “Exit Error” event as specified
by the SIA standard:
1. An Exit Delay point remains faulted at the end of Exit Delay.
2. Entry Delay starts. Keypads show DISARM NOW and the Entry
Tone sounds.