D9412GV4/D7412GV4/D7212GV4 Programming to Set Up Central Station Reporting | en 11
Bosch Security Systems, Inc. Quick Reference Guide F01U215242 | 01 | 2011.10
4 Programming to Set Up Central Station Reporting
4.1 Basic Telephone Set Up in RPS
1. Go to PANEL WIDE PARAMETERSPhone and Phone Parameters.
2. Enter the primary telephone number in the Phone 1 field.
3. If a secondary telephone number is required, enter it in the Phone 2 field.
4. Go to Panel Wide ParametersCommunicatorRoute Group 1.
5. Enter Phone 1 in the Primary Device field.
6. If a secondary telephone is required, enter Phone 2 in the Backup Device field.
4.2 Basic Internet Protocol (IP)
1. Go to PANEL WIDE PARAMETERSCommunicatorRoute Group 1 Primary Device.
2. Select SDI Address 88 Path 1.
3. Go to PANEL WIDE PARAMETERSSDI RPS/Enhanced CommEnable Enhanced
Communications to Yes.
4. Go to PANEL WIDE PARAMETEREnhanced Communications.
5. Select or enter the following values:
4.3 Account Number
In RPS, go to AREA WIDE PARAMETERS and enter the account number (up to 10 digits) in
the Account Number parameter.
NOTICE!
You can program these items using RPS and the steps listed below. You can also use keypad
programming (refer to the D9412GV4/D7412GV4/D7212GV4 Program Entry Guide (P/
N: F01U218312).
NOTICE!
Enhanced Communications settings usually follow the recommendations of the Central
Stations’ staff.
If using an ITS-DX4020-G for communication, refer to the ITS-DX4020-G Installation and
Operation Guide (P/N: F01U163066).
If using an B420 Ethernet Communication Module, refer to the B420 Ethernet Communication
Module Installation and Operation Guide (P/N: F01U215236).
Parameter Value
Enable Enhanced Communication YES
Path 1 Network Address IP or Network address of Central Station
receiver
Path 1 Port Number Port Number of Central Station receiver
Path 1 Poll Rate (seconds)
1
Poll rate recommended by Central Station
Path 1 ACK Wait Time 13 sec (default setting)
Path 1 Retry Count 5 (default Setting)
Path 1 Enable Anti-Replay Yes (default setting)
1
If the control panel is programmed to send a heartbeat poll to the central station, a rate of 75 sec
maintains the virtual link in most network configurations.
NOTICE!
Area 1 is the only area turned on by default.
Page view 10