50 en | Subsystem Maintenance RAID Subsystem DVA-16K | Installation Manual
F.01U.027.799 | V2 | 2008.08 Bosch Security System
6.5 Replacing a Faulty PSU Module
6.5.1 PSU Module Overview
Two (2) redundant PSU modules: The RAID subsystem is preinstalled with two (2) 460W,
fully redundant, hot-swappable PSU modules. These modules are located at the rear of
the subsystem.
PSU bracket: Each PSU module is permanently mounted in a two-level steel bracket, cre-
ating a single unit. The PSU is located in the upper level and a removable cooling module
is mounted in the lower level. When removing the PSU from the subsystem, the cooling
module is also being removed.
PSU printing mark: Before you insert a new PSU, be sure that it has the same printing
mark on its handle as that shown on the handle of a remaining PSU. Double-check to
avoid mixing a PSU of previous series. (See Figure 6.10)
Fig. 6.10 Label on the PSU Handle
Immediate replacement: When a PSU fails, it should be replaced immediately. However,
do not remove the PSU module unless a replacement is readily available. Removing a PSU
without a replacement will cause severe disruptions to the internal airflow and the sub-
system will overheat, possibly causing irreparable damage to some of the subsystem
components.
6.5.2 Replacing the PSU Module
To replace a PSU, please follow these steps:
1. Turn off the PSU. Using the power switch located at the top of the rear panel, directly
above the PSU module. (See Figure 6.11)
2. Remove the power cable that connects the RAID subsystem to the main power source.
The power socket is found on the left side of each power supply module. (See
Figure 6.11)
CAUTION!
Although the PSU modules are fully redundant, it is not advisable to run the RAID subsystem
with a single PSU module for an extended period of time. If the second PSU module fails, the
subsystem will be shut down.