Bosch FPD-7024 User Manual Page 85

  • Download
  • Add to my manuals
  • Print
  • Page
    / 122
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 84
RING COUNT
(01-15, 00=DIS) _______
Enter the information and press [#/Enter]. The previous window appears. An entry of [0/Prog]
[0/Prog] disables ring detection.
For acceptable programming selections for UL864 9
th
edition Listed applications, see
Programming features for UL864, 49.
Communication Tries
Shortcut: 0-PROG, 6-PROG ACC’NTS, 5-COMM. TRIES
The system default is to try ten times to communicate an event. Bosch recommends setting
this to five tries. This parameter determines after which attempt the system indicates a failure
condition. (After reporting a failure, the system continues to communicate until it reaches ten
times). Do not select 1 or a failure is indicated whenever a report is sent.
The following window appears:
COMM ATTMPTS (__)
(01-10): _______
Enter the information and press [#/Enter]. The previous window appears.
Machine Bypass
Shortcut: 0-PROG, 6-PROG ACC’NTS, 6-MACH BYPASS
The downloading computer must redial the control panel if an answering machine answered
the phone before the control panel. When this option is selected, if the control panel detects
the phone line ringing within one minute of when the last ringing cycle stopped, it answers on
the first ring and seizes the phone line. If an IP address is entered in for the Phone/IP number,
the control panel ignores this setting.
The following window appears:
MACHINE BYPASS
_______: YES (1) NO (0)
Enter the information and press [#/Enter]. The previous window appears.
ALT. COMM
Shortcut: 0-PROG, 6-PROG ACC’NTS, 7-ALTER COMM
This prompt is used with the B420 models, DX4010, DX4020 or ITS-DX4020-G.
If using the DX4010 select 1-serial; for all others, select 0-network. The following window
appears:
ALTER COMM (_)
0 – NETWORK
1 - SERIAL
PROG FORMATS
PROG FORMATS
1 - 4/2 ZONE REPT
2 - 4/2 RPT CODS
3 - BFSK RPT CDS
8.6.5
8.6.6
8.6.7
8.7
Fire Alarm Control Panels Control Panel Programming | en 85