Bosch FPD-7024 User Manual Page 60

  • Download
  • Add to my manuals
  • Print
  • Page
    / 122
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 59
AUTOMATIC TEST
1-TEST TIME
2-TEST FREQNCY
Press [1] to select Test Time. The following window appears:
AUTO TEST TIMEHHMM: _______
Enter the time followed by the [#/Enter] key.
Test Frequency
Shortcut: 0-PROG, 1-PROG TIME, 2-AUTO TEST
This feature allows you to program how often the automatic test reports are sent. The first
test is sent when the programmed test time matches the system time. Subsequent reports are
sent according to the selected interval.
The following window appears:
AUTOMATIC TEST
1-TEST TIME
2-TEST FREQNCY
Press [2] to select Test Frequency.
The following window appears:
AUTO FRQNCY ( )
1-4 HOURS
2-12 HOURS
3-24 HOURS
4-7 DAYS*
5-28 DAYS*
* For acceptable programming selections for UL864 9
th
edition Listed applications, see
Programming features for UL864, 49.
Press the number key that corresponds to your selection. The existing setting is displayed in
parentheses on the first line. After you have programmed the test frequency, the previous
window appears.
Daylight saving time
Shortcut: 0-PROG, 1-PROG TIME, 3-DAYLIGHT SAV
This feature enables automatic adjustment of system time for Daylight Saving Time. The dates
for the adjustment are pre-programmed in the system.
The following window appears:
DAYLIGHT SAV
1-DISABLE
2-ENABLE
Press [1] to select DISABLE or [2] to select ENABLE. After you have programmed this feature,
the previous window appears.
SECURITY
SECURITY
1-PINS
8.1.3
8.2
60 en | Control Panel Programming Fire Alarm Control Panels
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Page view 59
1 2 ... 55 56 57 58 59 60 61 62 63 64 65 ... 121 122

Comments to this Manuals

No comments