Installation Instructions Bosch IDS BOVA | 23
Bosch Thermotechnology Corp. | 12.2016
Data subject to change
15.7 Fault code table
Code Fault Description
E4 Temperature sensor fault(T3, T4, T5, TF)
E5 High/low voltage protection
E6 DC fan motor fault
E7 Compressor discharge sensor(T5) is seated fault
E9 EEPROM fault
Eb System lockup, 2 times (E6) protection in 10 minutes
H0 Communication fault in main control chip
H4 System lockup, 3 times (P6) protection in 60 minutes
H5 System lockup, 5 times (P2) protection in 100 minutes
H8 Pressure transducer(PT) fault
Hb High pressure(PT) protection in Heating
P0 High module radiator temperature (TF)protection
P1 High pressure switch(HPS)protection
P2 Low pressure(PT) Protection in cooling
P3 Compressor over current protection
P4 High compressor discharge temperature(T5) protection
P5 condensor coil temperature(T3) protection in cooling
P6 The IPM module protection
PH Low discharge superheat protection
F1 High pressure switch(HPS) fault
C3 The condensor coil sensor(T3) is seated fault in cooling
L0-L9 The IPM module protection (the same as P6,only for analysis)
AtL Ambient Temperature Limited
System Protection Status Codes
Indication under charge model
L Running indication under T3 limited condition
D Running indication under T5 limited condition
P Running indication under compressor ratio limited condition
F Running indication under Tf limited condition
C Running indication under current limited condition
U Running indication under low voltage limited condition
H Running indication under high pressure(PT) limited condition in heating
A Running indication under return oil model
dF Running indication under defrost model
Table 9