Installation Instructions Bosch IDS BOVA | 7
Bosch Thermotechnology Corp. | 12.2016
Data subject to change
2.3 Location restrictions
Ensure the top discharge area is unrestricted for at least 60 inches above the unit.
Do not locate outdoor unit near bedrooms since normal operational sounds may be
objectionable.
Position unit to allow adequate space for unobstructed airfl ow, wiring, refrigerant
lines, and serviceability.
Allow a minimum of 12 in. clearance on one side of access panel to a wall and a
minimum of 24 in. on the adjacent side of access panel.
Maintain a distance of 24 in. between units.
Position unit so water, snow, or ice from roof or overhang cannot fall directly on unit.
See Fig. 3 and Fig. 4.
Cold climate considerations (heat pump only)
Precautions must be taken for units being installed in areas where
snow accumulation and prolonged below-freezing temperatures occur.
Units should be elevated 3-12 inches above the pad or rooftop, depending
on local weather. This addi-tional height will allow drainage of snow and ice
melted durIng defrost cycle prior to its refreezlng. Ensure that drain holes
in unit base pan are not obstructed, preventing drainage of defrost water
(Fig. 5).
If possible, avoid locations that are likely to accu-mulate snow drifts. if not
possible, a snow drift barrier should be installed around the unit to prevent
a build-up of snow on the sides of the unit.
Min. 20” to
Shrubbery
Avoid Install
Near Bedrooms
Min. 60” Unrestricted
Access Panel
Min. 36
Unrestricted
Figure 3
Min. 20” to
Shrubbery
Min. 36” to
Shrubber
Access Panel
Figure 4
Min 12"
Snow
barrier
3- 12" Elevation
Snow legs
pad
Figure 5